SiBE34-802
3.1.4
Setting Contents and Code No.
Mode
Setting
No.
Switch
No.
Note 2
Filter contamination
heavy/light (Setting for
display time to clean air
filter)
0
(Sets display time to clean
air filter to half when there
is heavy filter
10
contamination.)
(20)
1
Long life filter type
Thermostat sensor in remote
2
controller
Display time to clean air filter calculation
3
(Set when filter sign is not to be displayed.)
11
7
Airflow adjustment
(21)
Optional accessories output selection (field
0
selection of output for adaptor for wiring)
ON/OFF input from outside (Set when ON/
1
OFF is to be controlled from outside.)
Thermostat differential changeover
2
(Set when remote sensor is to be used.)
VRV
12
3
OFF by thermostat fan speed
system
(22)
indoor
Automatic mode differential
unit
(automatic temperature differential
4
settings
setting for VRV system heat
recovery series cool/heat)
5
Power failure automatic reset
6
Airflow When Cooling Thermostat is OFF
High air outlet velocity
0
(Set when installed in place with
ceiling higher than 2.7 m.)
Selection of air flow direction (Set when
1
a blocking pad kit has been installed.)
Air flow direction adjustment (Set at
3
13
installation of decoration panel.)
(23)
4
Field set air flow position setting
Setting of the Static Pressure
5
Selection
6
External Static Pressure Settings
1
Thermostat OFF excess humidity
Direct duct connection
(when the indoor unit and heat
2
reclaim ventilation unit are
15
connected by duct directly.) ∗Note 6
(25)
3
Drain pump humidifier interlock selection
Field set selection for individual
5
ventilation setting by remote controller
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
3. Marked
4. Do not make settings other than those described above. Nothing is displayed for functions
5. "88" may be displayed to indicate the remote controller is resetting when returning to the
6. If the setting mode to "Equipped", heat reclaim ventilation fan conducts the fan residual
7. • The FXMQ50·63·80·100·125PVE cannot be set to 30Pa.
Test Operation
Setting Contents
Super
long life
filter
Long life
filter
Standard
filter
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
they cannot be set individually. Setting changes also cannot be checked.
are factory set.
the indoor unit is not equipped with.
normal mode.
operation by linking to indoor unit.
• The FXMQ40PVE cannot be set to 180 or 200Pa.
– VRV Indoor unit
Second Code No.(Note 3)
01
02
Approx.
Approx.
10,000
5,000
hrs.
hrs.
Approx.
Approx.
Light
Heavy
2,500
1,250
hrs.
hrs.
Approx.
Approx.
200 hrs.
100 hrs.
Super long life
Long life filter
filter
Use
No use
Display
No display
Completion of
OFF
airflow
adjustment
Indoor unit turned
ON by thermostat
Forced OFF
ON/OFF control
1°C
0.5°C
LL
Set fan speed
01:0
02:1
03:2
04:3
Not equipped
Equipped
LL air flow
Preset air flow
N
H
F (4 directions)
T (3 directions)
Equipped
Not equipped
Draft prevention
Standard
High static
Standard
pressure
01:30
02:50
03:60
04:70
09:120 10:130 11:140 12:150 13:160 14:180 15:200
Not equipped
Equipped
Not equipped
Equipped
Not equipped
Equipped
Not equipped
Equipped
Field Setting
03
04
Start of airflow
adjustment
Operation
Malfunction
output
output
External protection
device input
05:4
06:5
07:6
08:7
S
W (2 directions)
Ceiling Soiling
prevention
05:80
06:90
07:100 08:110
*7
Details
No.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
(21)
(22)
91