Field Setting
BRC1D528
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual for each optional accessory.
1. When in the normal mode, press the "
2. Select the desired MODE NO. with the "
3. During group control, when setting by each indoor unit (mode No. 20, 21, 22 and 23 have
4. Push the "
5. Push the "
6. Push the "
7. Push the "
(Example)
If during group setting and the time to clean the air filter is set to FILTER CONTAMINATION -
HEAVY, SET MODE NO. to "10", FIRST CODE NO. to "0", and SECOND CODE NO. to "02".
Notes :
1. Setting is carried out in the group mode, however, if the mode number inside the
2. The SECOND CODE number is set to "01" when shipped from the factory.
3. Do not make any settings not given in the table.
4. Not displayed if the indoor unit is not equipped with that function.
5. When returning to the normal mode, "88" may be displayed in the LCD in order for the
6. It is not possible to change field settings on the remote controller that is set to "sub".
88
UNIT NO.
FIRST
CODE NO.
SECOND
CODE NO.
4
3
1
7
FIELD SET MODE is entered.
been selected), push the "
operation is unnecessary when setting by group.)
" upper button and select FIRST CODE NO.
" lower button and select the SECOND CODE NO.
" button once and the present settings are SET.
" button to return to the NORMAL MODE.
parentheses is selected, indoor units can also be set individually.
remote controller to initialize itself.
UNIT No.
GROUP
SETTING
6
5
2
" button for a minimum of four seconds, and the
" button.
" button and select the INDOOR UNIT NO. to be set. (This
SiBE34-802
MODE NO.
FIELD
SET
MODE
Test Operation