Ceiling Mounted Duct Type
1-1 TECHNICAL SPECIFICATIONS
Cooling
Capacity
Heating
Cooling
Power Input
Heating
Casing
Material
Height
Dimensions
Unit
Width
Depth
Weight
Unit
Nr of Rows
Fin Pitch mm
Heat
Dimensions
Exchanger
Face Area m²
Nr of Stages
Fan
Type
High high m³/min
Air Flow Rate Cooling
High
Low
High
External static
Standard Pa
pressure
Low
Fan
Output
(high)
Motor
Drive
Type
Liquid (OD)
Diameter mm
Piping
Type
connections
Gas
Diameter mm
Drain
Diameter mm
Refrigerant control
Temperature control
Safety devices
Standard Accessories
Notes
Specifications
FXMQ40PVE
FXMQ50PVE
kW
4.5
kW
5.0
0.194 (1)
0.215 (1)
kW
0.193 (2)
0.214 (2)
kW
0.182
mm
300
mm
700
mm
700
kg
28
3
1.75
0.148
16
16
m³/min
13
m³/min
11
Pa
160
100
Pa
30
W
140
6.35
12.7
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washer, Screws, Insulation for fitting,
Nominal cooling capacities are based on following conditions: return air temperature: 27°CDB/19°CWB; outdoor
temperature: 35°CDB; standard external static pressure: 100Pa; equivalent refrigerant piping: 7.5m (horizontal)
Nominal heating capacities are based on following conditions: return air temperature: 20°CDB; outdoor temperature:
7°CDB/6°CWB; standard external static pressure: 100Pa; equivalent refrigerant piping: 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable in 13 or 14 stages within the ( ) range by the remote control.
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric
FXMQ63PVE
5.6
7.1
6.3
8.0
0.230 (1)
0.229 (2)
0.203
0.218
Galvanised steel plate
300
300
1,000
1,000
700
700
36
36
3
3
1.75
1.75
0.249
0.249
16
16
Sirocco fan
18
19.5
16.5
17.5
15
16
200
200
100
100
50
50
350
350
Direct drive
Flare connection
9.52
9.52
Flare connection
15.9
15.9
VP25 (I.D. 32/O.D. 25)
Electronic expansion valve
Microprocessor thermostat for cooling and heating
Fuse, Fan driver overload protector
Clamp metal, Air discharge flange, Air suction flange
method(gravity method) 50% or more.
Specifications
FXMQ80PVE
FXMQ100PVE
9.0
11.2
10.0
12.5
0.298 (1)
0.376 (1)
0.297 (2)
0.375 (2)
0.286
0.364
300
300
1,000
1,400
700
700
36
46
3
3
1.75
1.75
0.249
0.383
16
16
25
32
22.5
27
20
23
200
200
100
100
50
50
350
350
9.52
9.52
15.9
15.9
FXMQ125PVE
14.0
16.0
0.461 (1)
0.460 (2)
0.449
300
1,400
700
46
3
1.75
0.383
16
39
33
28
200
100
50
350
9.52
15.9
21