Daikin RXYSQ4-5-6PA7V1B Service Manual page 116

Vrv iii-s
Table of Contents

Advertisement

SiBE34-802
Caution
Capacity Setting after changing the main PC Board(A1P) to spare parts PC Board
When you change the main PC Board(A1P) to spare parts PC Board, please carry out the
following setting.
Please Attach the Capacity Setting Adaptor corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adaptor
Position of Attaching the Capacity Setting Adaptor
RXYSQ4 / 5 / 6PA7Y1B
RXYSQ4 / 5 / 6PA7V1B
Test Operation
Capacity Class
4 (112)
CAPACITY SETTING ADAPTOR (for 100/J112)
5 (140)
CAPACITY SETTING ADAPTOR (for 125/J140)
6 (160)
CAPACITY SETTING ADAPTOR (for 140/J160)
X51A
Note
Field Setting
X51A
105