Daikin RXYSQ4-5-6PA7V1B Service Manual page 30

Vrv iii-s
Table of Contents

Advertisement

SiBE34-802
Ceiling Mounted Built-in Type
1-1 TECHNICAL SPECIFICATIONS
Capacity
Cooling
(Conditions
Heating
specified in 1)
Cooling
Power input
(Nominal)
Heating
Colour
Casing
Material
Height
Packing
Width
Depth
Dimensions
Height
Unit
Width
Depth
Unit
Weight
Packed Unit
Required Ceiling Void
Length
Nr of Rows
Fin Pitch mm
Dimensions
Nr of Passes
Face Area m²
Heat
Exchanger
Nr of Stages
Empty Tubeplate Hole
Tube type
Fin type
Fin
Treatment
Type
Fan
Quantity
High
Cooling
Low
Air Flow Rate
High
Heating
Low
High
External static
Standard Pa
pressure
Low
Quantity
Fan
Model
Steps
Motor
Output
(high)
Drive
Refrigerant
Name
Sound
Sound Level
Cooling
power
(nominal)
High
Sound
Cooling
Pressure
Low
High
Sound
Heating
Pressure
Low
Type
Liquid (OD)
Diameter mm
Type
Piping
Gas
connections
Diameter mm
Drain
Diameter mm
Heat Insulation
Model
Colour
Height
Decoration
Panel
Dimensions
Width
Depth
Weight
Drain-up Height
Air Filter
Air direction control
Refrigerant control
Temperature control
Safety devices
Standard Accessories
Notes
Specifications
FXSQ20M8V3B
kW
2.20
kW
2.50
kW
0.110
kW
0.090
mm
354
mm
742
mm
936
mm
300
mm
550
mm
800
kg
30
kg
34
mm
350
mm
300
3
1.75
3
0.088
14
1
m³/min
9.00
m³/min
6.50
m³/min
9.00
m³/min
6.50
Pa
125
105
Pa
96
1
D18H3AA1V1
W
50
dBA
50.0
dBA
32.0
dBA
28.0
dBA
32.0
dBA
28.0
6.35
12.7
32
BYBS32DJW1
mm
55
mm
650
mm
500
kg
3
mm
600
Metal clamp for drain hose, Paper pattern for installation, Drain hose, Insulation for fitting, Washer for hanger bracket,
Screws for duct flanges, Screws for fixing the paper pattern for installation, Fuse, Installation and operation manual
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
The external static pressure is changeable : change the connectors inside the electrical box, this pressure means :
The external static pressure is changeable : change the connectors inside the electrical box, this pressure means :
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The sound pressure values are mentioned for a unit installed with rear suction
FXSQ25M8V3B
FXSQ32M8V3B
2.80
3.60
3.20
4.00
0.110
0.114
0.090
0.094
Non painted
Galvanised steel
354
354
742
742
936
936
300
300
550
550
800
800
30
30
34
34
350
350
300
300
3
3
1.75
1.75
3
3
0.088
0.088
14
14
14
Hi-XSS (7)
Symmetric waffle louvre
Hydrophilic
Sirocco fan
1
1
9.00
9.50
6.50
7.00
9.00
9.50
6.50
7.00
125
104
105
88
96
78
1
1
D18H3AA1V1
D18H3AA1V1
step motor
50
50
Direct drive
R-410A
50.0
51.0
32.0
33.0
28.0
28.0
32.0
33.0
28.0
28.0
Flare connection
6.35
6.35
Flare connection
12.7
12.7
32
32
Both liquid and gas pipes
BYBS32DJW1
BYBS32DJW1
White (10Y9/0,5)
55
55
650
650
500
500
3
3
600
600
Resin net with mold resistance
Up and downwards
Electronic expansion valve
Microprocessor thermostat for cooling and heating
PC board fuse, Drain pump fuse, Fan motor thermal fuse
equivalent refrigerant piping : 8m, level difference : 0m.
equivalent refrigerant piping : 8m, level difference : 0m.
High static pressure -standard - low static pressure
High static pressure -standard
Specifications
FXSQ40M8V3B
FXSQ50M8V3B
4.50
5.60
5.00
6.30
0.127
0.143
0.107
0.123
354
354
892
892
936
936
300
300
700
700
800
800
30
31
34
35
350
350
450
450
3
3
1.75
1.75
4
4
0.132
0.132
14
14
1
1
11.50
15.00
9.00
11.00
11.50
15.00
9.00
11.00
116
136
98
114
85
99
1
1
D18H2AC1V1
D18H2AB1V1
65
85
56.0
58.0
33.0
35.0
29.0
31.0
33.0
35.0
29.0
31.0
6.35
6.35
12.7
12.7
32
32
BYBS45DJW1
BYBS45DJW1
55
55
800
800
500
500
3.5
3.5
600
600
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxysq4-5-6pa7y1b

Table of Contents