Honeywell IAQPoint2 User Manual page 1452

Air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

Available languages

Available languages

Device Communication
FLN Network Strategies
Analog Inputs
SENSOR
TYPE
2
3
5
20
Other analog inputs include: GAS CONC (point 4) shows the current gas
concentration. SENSOR TEMP (point 11) gives the temperature inside
the detector. RUN TIME (point 12) is the number of days the sensor has
been on.
Digital Inputs
20
SENSOR TYPE (point 3) shows the gas type detected
by the detector, according to the table below:
Target Gas
CO
Carbon monoxide
O2
Oxygen
NO2
Nitrogen dioxide
COMB
Combustible gases
ALR LO FLAG (Point 90) and ALR HI FLAG (Point 91)
are the main physical DIs on the 901T. They
correspond to a specific gas concentration limit. the low
level, ALR LO FLAG (point 90), is set when the gas
concentration reaches the ALR LO MAX level (point 8),
and cleared when the gas concentration returns under
the ALR LO MIN level (point 7). In the same way, the
high level alarm, ALR HI FLAG (point 91) is set when
the gas concentration reaches the ALR HI MAX level
(point 10) and cleared when the gas concentration is
lower than ALR HI MIN (point 9).
901T User Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E3point

Table of Contents