Honeywell IAQPoint2 User Manual page 1543

Air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

Available languages

Available languages

WIRING DETAILS
System Wiring
Output Loop-Powered Operation
(Factory Setting)
The 4-20 mA output is factory set for loop-powered operation and
requires a power source of 12 Vdc to 30 Vdc. The overall impedance
depends on the voltage supplied at the 4-20 mA loop. Set jumpers on
JP4 at 2-3, 4-5 and 6 for this type of configuration.
Permitted Impedance in the 4-20 mA Loop
Voltage Source Applied
12 Vdc
16 Vdc
20 Vdc
24 Vdc
30 Vdc
24
301EM User Manual
Total Impedance
400 Ohms
600 Ohms
800 Ohms
1,000 Ohms
1,300 Ohms