Honeywell IAQPoint2 User Manual page 1359

Air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

Available languages

Available languages

LONWorks Configuration
LON Objects Descriptions
LonWorks is a communications protocol developed by Echelon
Corporation which facilitates peer-to-peer communications in a control
network. Information on LonWorks can be found at www.echelon.com.
Information on LonMark can be found at www.lonmark.org.
The IAQPoint can be directly integrated within a LonWorks network using
an optional, integrated circuit board. All gas readings, faults and other
sensor data are transmitted via the LonWorks protocol. (If your IAQPoint
does not have the Temperature and Relative Humidity sensor option,
objects 1040 and 1050 will not be present.)
Please refer to our Website's IAQPoint section
(www.honeywellanalytics.com) to obtain the XIF (External Interface
File) file. This is an ASCII file used by network configuration tools
to detail the resources of the IAQPoint LON device.
Object 1040: Temperature Measurement Variables
LON Variable Name
SNVT_temp_p nvoHVACTemp
SCPTmaxSendTime(49)
SNVT_time_sec nciMaxSendtime
SCPTminSendTime(52)
SNVT_time_sec nciMinsendtime
SCPTminDeltaTEMP(64)
SNVT_temp_p nciMinDelta
SNVT_temp_p nvoTempSetPt
Annex A - BACnet, LON and Modbus Objects
Reports the temperature reading (range:
-20.0 to 50.0 ºC).
Determines the maximum delay in
seconds before the sensor object
updates its output variables
Determines the minimum delay in
seconds before the sensor object
updates its output variables
Indicates the minimum difference
between successive measurements
required to cause an update of the output
variable
Reports the desired temperature setpoint
Default value 22ºC
IAQPoint User Manual
LONWorks Configuration
Description
43

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E3point

Table of Contents