9.2

LED status check

The table below describes details for the LED statuses.
LED display
Color
POWER
Green
RUN
Green
ERR.
Red
L RUN
Green
L ERR.
Red
SD
Green
RD
Green
The POWER, RUN, L RUN, SD and RD LEDs are ON while the data link status is normal.
When the RUN LED does not light up and the hardware test is not set, the hardware may have an error.
For repair, contact your local Mitsubishi Electric distributor.
Status
OFF
Power is not being supplied from the external power supply.
ON
Power is being supplied from the external power supply.
OFF
64CCL has failed.
ON
Under 64CCL normal operation.
OFF
No errors.
Error in the settings, error in the parameter details, error with the communication,
ON
errors with the hardware.
OFF
Offline.
ON
Data link is being executed.
OFF
No communication error.
The switch setting was changed after start.
Flicker
There is no terminating resistor.
Influence from noise.
There is a data linking error.
ON
There is a setting error.
OFF
Data is not being sent.
ON
Data is being sent.
OFF
Data is not being received.
ON
Data is being received.
→ For details on troubleshooting by LED, refer to the master unit manual.