Mitsubishi FX3U-64CCL User Manual page 58

Programmable controller
Hide thumbs Also See for FX3U-64CCL:
Table of Contents

Advertisement

FX
-64CCL User's Manual
3U
BFM No.
SW No.
Name
Module
#866
SW0062
operating
status
Host
#872
SW0068
parameter
status
Switch setting
#874
SW006A
status
Max. link scan
#877
SW006D
time
Current
#878
SW006E
scan time
Min. link scan
#879
SW006F
time
#912
SW0090 Line status
Parameter
#1096
SW0148
mode
Host
#1097
SW0149
parameter
mode
52
Stores the operation setting status of the module.
0: OFF
1: ON
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0 0 0
0
0
Stores the parameter setting status.
0 : Normal
Other than 0: Stores the error code (Refer to error code).
Stores the switch setting status.
0 : Normal
Other than 0: Stores the error code (Refer to error code).
Update timing: Updated individually without regard to link special relays (SB).
Stores the maximum value of the link scan time (in 1 ms units).
Update timing: Updated individually without regard to link special relays (SB).
link
Stores the current value of the link scan time (in 1 ms units).
Update timing: Updated individually without regard to link special relays (SB).
Stores the minimum value of the link scan time (in 1 ms units).
Update timing: Updated individually without regard to link special relays (SB).
Stores the line status.
0: Normal
1: Data link cannot be performed (disconnected)
Update timing: When SB0090 changes.
Indicates in which mode the network is operating.
0: Remote net ver.1 mode
2: Remote net ver.2 mode
Indicates in which mode the host is operating.
0: Remote net ver.1 mode
2: Remote net ver.2 mode
Description
0
0
0
Number of occupied stations
00 : Occupies 1 station
10 : Occupies 2 stations
11 : Occupies 3 stations
01 : Occupies 4 stations
Expanded cyclic setting
00 : Single
01 : Double
10 : Quadruple
11 : Octuple
7 Buffer Memory
7.2 Buffer memory details
Applicability
(
: Applicable,
: Not
applicable)