5.3

CC-Link wiring

5.3.1

CC-Link cabling

Use dedicated CC-Link cables in the CC-Link system.
If any other cable is used, the performance of the CC-Link system cannot be guaranteed.
For the specifications of CC-Link dedicated cables, please refer to the CC-Link catalog published by the
CC-Link Partner Association or the following website:
CC-Link Partner Association website: http://www.cc-link.org/
5.3.2

Wiring with CC-Link cabling

Wire the 64CCL to the CC-Link with CC-Link network dedicated cables as follows.
• Wiring example
Termi-
Master
nating
unit
resistor
(Blue)
DA
(White)
DB
(Yellow)
DG
SLD
FG
- Connect the [DA] and [DA] terminals, [DB] and [DB] terminals and [DG] and [DG] terminals of each
station respectively with CC-Link dedicated cables.
- Connect the [SLD] terminal of each station to the shielded area of the CC-Link dedicated cables.
- Execute Class D grounding to the [FG] terminal of each station.
- Each station can be wired without regard to the station number sequence.
- Connect a terminating resistor between the [DA] and [DB] terminals of the terminal station. The
terminating resistor is packed together with the master unit.
- The maximum transmission distance and distance among stations for the CC-Link system varies
depending on the specified transmission rate. For details, follow the specifications described in the
manual of the CC-Link master unit.
FX
-64CCL
3U
(Blue)
DA
(White)
DB
(Yellow)
DG
CC-Link
SLD
Dedicated
Cable
(Blue)
(Blue)
(White)
(White)
(Yellow)
(Yellow)
CC-Link
Dedicated
Cable
5 Wiring, Start-up procedure
5.3 CC-Link wiring
Other
Termi-
station
nating
resistor
DA
DB
DG
SLD
FG
29
1
2
3
4
5
6
7
8
9
A