Troubleshooting; Troubleshooting Procedure - Mitsubishi FX3U-64CCL User Manual

Programmable controller
Hide thumbs Also See for FX3U-64CCL:
Table of Contents

Advertisement

FX
-64CCL User's Manual
3U
9.

Troubleshooting

This chapter describes major problems that may occur during the CC-Link system construction and lists the
items to be checked and confirmed for troubleshooting.
9.1

Troubleshooting procedure

The table below lists the items to be checked and confirmed for each troubleshooting problems.
Problem
64CCL cannot be linked.
Master
station
receive data stored in the
remote
inputs
remote registers (RWr) of
the 64CCL.
Master station cannot turn
ON/OFF
remote
(RY) of 64CCL, or cannot
write
data
to
registers (RWw) of 64CCL.
60
Checkpoint
Is external power supply (24V) supplied?
Is there an error in the station number setting, the
number of occupied stations / expanded cyclic
setting, or transmission rate / hardware test setting?
Can the master station carry out link stop?
Is it a reserved station?
Is the CC-Link cable wired correctly?
Is the 64CCL performing data link?
cannot
(RX)
or
Is data being written to the correct addresses of the
remote inputs (RX) or remote registers (RWr)?
Is it a reserved station?
Are there any station numbers that are overlapped? Check the station number setting.
Is the 64CCL performing data link?
outputs
Is data being read from the correct addresses of the
remote
remote outputs (RY) or remote registers (RWw)?
Is it a reserved station?
Are there any station numbers that are overlapped? Check the station number setting.
9.1 Troubleshooting procedure
→ For details, refer to the master unit manual.
The POWER LED display is checked.
The following description is checked.
Check the error code BFM#29 b0-b2.
Check the switch setting status (SW006A).
Check the master station setting
The LED display of the master station is checked.
The setting of the master station is checked.
Cable wiring is checked.
Use the following method:
Check the LED display of the unit.
Check the station data link status of the master
station (SW0080).
Check the sequence program.
Check the parameters.
Use the following method:
Check the LED display of the unit.
Check the station data link status of the master
station (SW0080).
Check the sequence program.
Check the parameters.
9 Troubleshooting
Action

Advertisement

Table of Contents
loading

Table of Contents