SECTION 4 SYSWAY (E5@J and E5@X Format) Communications Procedures

■ SYSWAY Command Lists

Header
Category
code
Selecting Communi-
MB
cations Writing
Write mode selection
ME
MA
Save operation/
MW
adjustment set value
Writing set values
WS
W%
W%
WB
WN
WV
WI
WW
Read set value and
RS
manipulated variable
R%
monitor
R%
RB
RN
RV
RI
RW
RO
Read SP upper and
RL
lower limit values
Read process value
RX
Read the heater current
RZ
monitor
Read the initial status
RU
• No commands will be accepted and no responses will be returned when a memory error (RAM error)
has occurred or during initialization (until the process value is recognized after power is turned ON).
• When a write operation is performed while there is a memory error (EEPROM error), data will not be
written and the command will end with "normal completion." Read operations will be executed
normally.
Note 1.The process value read range is the same as the input's display range.
Note 2.Status (last 4 bytes)Note 3. Status (first 2 bytes)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0 0 0 0
• Overflow: Set 1 when the heater current value is greater than 55.0 A.
• Display hold: Set 1 when the control output ON time is less than 190 ms. The previous heater current
value is held.
4-4
Data
Command
code
01
Select communications writing
01
Select backup mode
01
Select RAM write mode
01
Save operation/adjustment set
value
01
Write set point
01
Write alarm value 1
02
Write alarm value 2
01
Write proportional band
01
Write integral time
01
Write derivative time
01
Write temperature input shift values
01
Write heater burnout detection
01
Read set point
01
Write alarm value 1
02
Write alarm value 2
01
Read proportional band
01
Write integral time
01
Write derivative time
01
Write temperature input shift values
01
Write heater burnout detection
01
Read MV monitor
01
Read SP upper and lower limit val-
ues
01
Read process value
01
Heater current value monitor
01
Read the initial status
Bit position
0
0 0 0
Overflow
Display hold
Data
R/W
length
Write
4B
Write
None
Write
4B
Read
4B
Read
8B
Read
8B
Read
8B
Read
5B
Bit position
7 6 5 4 3 2 1 0
0 0 0 0 0 0
Control
Output operation:
Remarks
Read both
upper/lower limit
values at once
See note 1.
See note 2.
See note 3.
1
0
ON/OFF PID
Direct Reverse