SECTION 2 CompoWay/F Communications Procedures
■ Read Controller Attributes
2-12
This service reads the model number and communications buffer size.
Service Request PDU
MRC SRC
0 5 0 3
2
2
Service Response PDU
MRC SRC
Response
code
0 5 0 3
2
2
4
(1) Model Number
The model number is expressed in 10-byte ASCII. When 10 bytes are
not required, pad the remaining bytes with spaces.
Example: The following model number is used for the E5CN-Q2HH03T
(voltage output, two alarm outputs, two heater burnout detection inputs,
communications functions, and multiple TC/Pt inputs).
e 5 c n - Q 2 H H O
(2) Buffer Size
The communications buffer size is expressed in 2-byte hexadecimal,
and read after being converted to 4-byte ASCII.
Buffer size: 40 bytes (= H'0028)
(3) Response Code
Normal Completion
Response code
0000
Normal completion
Error Occurred
Response code
1001
Command too long
2203
Operation error
Model No.
10
Name
Description
No errors were found.
Name
Description
The command is too long.
EEPROM error
Buffer
size
0 0 2 8
4