Omron E5CN Manual page 49

Digital temperature controller with 11-segment display
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

SECTION 3 Communications Data for CompoWay/F and SYSWAY
Vari-
Ad-
able
Parameter name
dress
type
C3
000A
Control period (heat)
C3
000B
Control period (cool)
C3
000C
Direct/reverse opera-
tion
C3
000D
Alarm 1 type
C3
000E
Alarm 2 type
C3
000F
Alarm 3 type
(See note 2.)
3-8
Setting (monitor) value
H'00000000 (0): 0.5
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0): 0.5
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
H'00000000 (0):
Alarm function OFF
H'00000001 (1):
Upper and lower-limit alarm
H'00000002 (2):
Upper-limit alarm
H'00000003 (3):
Lower-limit alarm
H'00000004 (4):
Upper and lower-limit range alarm
H'00000005 (5):
Upper and lower-limit alarm with standby
sequence
H'00000006 (6):
Upper-limit alarm with standby sequence
H'00000007 (7):
Lower-limit alarm with standby sequence
H'00000008 (8):
Absolute-value upper-limit alarm
H'00000009 (9):
Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm with
standby sequence
H'0000000B (11): Absolute-value lower-limit alarm with
standby sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'00000000 (0):
Alarm function OFF
H'00000001 (1):
Upper and lower-limit alarm
H'00000002 (2):
Upper-limit alarm
H'00000003 (3):
Lower-limit alarm
H'00000004 (4):
Upper and lower-limit range alarm
H'00000005 (5):
Upper and lower-limit alarm with standby
sequence
H'00000006 (6):
Upper-limit alarm with standby sequence
H'00000007 (7):
Lower-limit alarm with standby sequence
H'00000008 (8):
Absolute-value upper-limit alarm
H'00000009 (9):
Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm with
standby sequence
H'0000000B (11): Absolute-value lower-limit alarm with
standby sequence
Same settings as the alarm 2 type
Level
Initial set-
ting