SECTION 6 Communications Data for Modbus
Address
Parameter name
0D06
Linear current output
0D1E
SP upper limit
0D20
SP lower limit
0D22
Standard or Heating and
cooling
0D24
Direct/reverse operation
0D28
PID/OnOff
0D2A
ST
0D2C
Program pattern
0E00
Transfer output type
0E0C
Control output 1 assign-
ment
0E0E
Control output 2 assign-
ment
0E14
Event input assignment 1
6-8
Setting (monitor) value
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
The range of values (without decimal point) is as follows:
Temperature: SP lower limit + 1 to Input range upper limit
Analog: SP lower limit + 1 to scaling upper limit
The range of values (without decimal point) is as follows:
Temperature: Input range lower limit to SP upper limit − 1
Analog: Scaling lower limit to SP upper limit − 1
H'00000000 (0): Standard
H'00000001 (1): Heating and cooling
H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
H'00000000 (0): ON/OFF
H'00000001 (1): 2 degrees of freedom PID control
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT
H'00000000 (0): OFF
H'00000001 (1): Set point
H'00000002 (2): Set point during SP ramp
H'00000003 (3): PV
H'00000004 (4): MV monitor (heating)
H'00000005 (5): MV monitor (cooling)
When control output 1 is a linear output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
When control output 1 is a pulse output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output (See note 5.)
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output (See note 5.)
H'00000000 (0): None
H'00000001 (1): RUN/STOP (Cannot be set if the "Number
of multi-SP uses" is set to 1 or 2.)
Level
Initial set-
ting
Advanced
function
setting