Address
Parameter name
0500
Operation/adjustment
protect
0502
Initial setting/communi-
cations protect
0504
Setup change protection
0508
Move to protect level
050A
Password to move to pro-
tect level
050C
Parameter mask enable
Setting (monitor) value
H'00000000 (0): No restrictions in operation and adjustment
levels
H'00000001 (1): Move to adjustment level is prohibited.
H'00000002 (2): Display and change of only "PV" and "PV/
SP" parameters is allowed.
H'00000003 (3): Display of only "PV" and "PV/SP" parame-
ters is allowed.
H'00000000 (0): Move to initial setting/communications set-
ting level is allowed. (Move to advanced
function setting level is displayed.)
H'00000001 (1): Move to initial setting/communications set-
ting level is allowed. (Move to advanced
function setting level is not displayed.)
H'00000002 (2): Move to initial setting/communications set-
ting level is prohibited.
H'00000000 (0): OFF (Changing of setup on controller dis-
play is allowed.)
H'00000001 (1): ON (Changing of setup on controller display
is prohibited.)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
(Can only be set. The monitor value is always H'00000000.)
H'00000000 (0): OFF
H'00000001 (1): ON