Consequently, when the "communications writing" parameter setting is
changed to "OFF" (disabled), the parameters in the operation/
adjustment levels (excluding read-only parameters) are written to
EEPROM even if the RAM write mode is set to "disabled."
● RAM Data
This command writes the parameters in the operation/adjustment levels
(excluding read-only parameters) to EEPROM. The setting can be
accepted in both setup area 0 and setup area 1.
● Software Reset
Restarts processing from the point when power is turned ON. The
setting can be accepted in both setup area 0 and setup area 1. No
response will be returned for this operation.
● Move to Setup Area 1
This command moves to "setup area 1" and can be accepted at both
setup areas 0 and 1. If the "initial setup/communications protection" is
set to "2," an "operation error" will be generated, and the move to setup
area 1 will be prohibited.
When this move is carried out from setup area 0, the display indicates
the "input type" in the "initial setting level." When this operation
command is executed in setup area 1, the display will not change.
◆ Moving to Setup Area 1 in Manual Mode
When this operation command is issued in manual mode, an
"operation error" will be generated, and the move to setup area 1 will
be prohibited.
● Move Protect Level
This command moves to the "protect level" and can be accepted only in
setup area 0. When this command is issued in setup area 1, an
"operation error" will be generated, and the move to the protect level will
be prohibited.
◆ Moving the Protect Level in Manual Mode
When this operation command is issued in manual mode, an
"operation error" will be generated, and the move to the protect level
will be prohibited.