Introduction
With respect to transportation and storage conditions, the S7-1500 automation system fulfills
the requirements in accordance with IEC 61131-2. The following statements apply to
modules that are transported and stored in the original packaging.
Shipping and storage conditions for modules
Table 15- 7
Type of condition
Free fall (in shipping package)
Temperature
Barometric pressure
Relative humidity
Sinusoidal vibrations in accordance with
IEC 60068-2-6
Shock in accordance with IEC 60068-2-27
170
Shipping and storage conditions for modules
Permissible range
≤ 1 m
from -40 °C to +70 °C
1080 hPa to 660 hPa (corresponds to an altitude
of -1000 m to 3500 m)
5% to 95%, without condensation
5 - 9 Hz: 3.5 mm
9 - 500 Hz: 9.8 m/s
2
250 m/s
, 6 ms, 1000 shocks
2