Table 6-2 Current Output Calibration Procedure - Honeywell UDC3200 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3200:
Table of Contents

Advertisement

Procedure
The procedure for calibrating the Current Output is listed in Table 6-2. Make sure LOCK
in the Tuning Set Up group is set to NONE. (See Subsection 3.4 – Tuning Set Up Group.)
Step
Operation
1
Enter Calibration
Mode
Calibrate 0 %
2
3
Calibrate 100 %
4
Exit the
Calibration Mode
12/04

Table 6-2 Current Output Calibration Procedure

Press
Upper Display = CALIB
Setup
Setup
Lower Display = CURRENT
until you see
You will see:
Function
Function
Function
Upper Display =
Lower Display = ZERO VAL
Until the desired 0 % output is read on the milliammeter,
or
use the values shown below depending on the action of
your controller. Normally, this will be the setting that
produces 4 mA.
This stores the 0 % value and
Function
Function
Function
you will see:
Upper Display =
Lower Display = SPAN VAL
Until the desired 100 % output is read on the milliammeter,
or
use the values shown below depending on the action of
your controller. Normally, this will be the setting that
produces 20 mA.
The controller stores the span value.
Function
Function
Function
To exit the calibration mode.
Lower
Lower
Lower
Display
Display
Display
UDC3200 Universal Digital Controller Product Manual
Result
A Value
A Value
Output Calibration
145