Communications; Table 10-18 Set-Up Group - Communications - Honeywell UDC3200 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3200:
Table of Contents

Advertisement

10.7.10

Communications

Table 10-18 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Communications.
Parameter
Description
Hex
Shed Time
004F
Shed Mode and
00A2
Output
Shed Setpoint
00A3
Recall
Computer
005A
Setpoint Ratio
Computer
005B
Setpoint Bias
Communication
004D
Address
Communications
00E7
Type
IR Port Enable
00F1
Baud Rate
00E8
Transmit Delay
004E
Floating Point
00E9
Byte Order
Shed Enable
00EA
Shed Time
009A
Comm Data
00A1
Units
12/04
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-18 Set-up Group – Communications
Register
Data
Address
Type
Decimal
79
INT
162
INT
163
INT
90
FP
91
FP
77
FP
231
INT
241
INT
232
INT
78
FP
233
INT
234
INT
154
INT
161
INT
UDC3200 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0 = No Shed
1 = 255 sample periods
R/W
0 = Last Mode and Last Output
1 = Manual Mode, Last Output
2 = Manual Mode, Failsafe Output
3 = Automatic Mode
R/W
0 = To Last Local Setpoint used
1 = CSP
R/W
–20.00 to 20.00
R/W
–999 to 9999.
R/W
1 - 99
R/W
0 = None
1 = Disable
2 = RS-485 Modbus
3 = Ethernet
R/W
0 = Disable
1 =- Enable
R/W
0 = 4800
1 = 9600
2 = 19200
3 = 38400
R/W
Response Delay in ms
(1 to 500) +6ms
R/W
0 = Big Endian
1 = Big Endian Byte Swap
2 = Little Endian
3 = Little Endian Byte Swap
R/W
0 = Enable
1 = Disable
R/W
0 = No Shed
1 = 255 sample periods
R/W
0 = Percent
1 = Engineering Units
215