10 Modbus Read, Write and Override Parameters plus

10.1 Overview

Introduction
This section contains information concerning Reading, Writing, and Overriding
parameters in the UDC3200 Process Controller. There are two types of parameters:
Data Transfer—These parameters include reading control data, option status, and
reading or changing setpoints.
Configuration Data—All the configuration data is listed in the order in which it
appears in the controller.
Each type of parameter has the identifying codes listed with it.
What's in this section?
The following topics are covered in this section.
10.1
Overview
10.2
Reading Control Data
10.3
Read Options Status
10.4
Miscellaneous Read Onlys
10.5
Setpoints
10.6
Using a Computer Setpoint (Overriding Controller Setpoint)
10.7
Configuration Parameters
10.8
Modbus RTU Exception Codes
General Information
Non-volatile Memory Retention
This controller uses non-volatile memory to store configuration data. These
memories are guaranteed to retain data for a minimum of ten years as long as the data
is not written and erased more than 10,000 times. In order not to exceed this number,
it is strongly recommended that configurations which change rapidly such as
Computer Setpoint use the Override feature which does not affect non-volatile
memory.
12/04

Modbus Read, Write and Override Parameters plus Exception Codes

Exception Codes
TOPIC
UDC3200 Universal Digital Controller Product Manual
See Page
185
186
187
188
189
190
191
219
185