10.7.5

Output Algorithms

Table 10-13 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Output.
Parameter
Description
Hex
Output
00A0
Algorithm
Relay Cycle
00BE
Time
Increments
Motor Time for
004B
Positional
Proportional
Relay Output
00F3
Action
Current Range
0099
for Current
Duplex
Current Output
00F2
(Auxiliary
Output Mode)
Current Output
00EA 235
Range
12/04
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-13 Set-up Group – Output
Register
Data
Address
Type
Decimal
160
INT
190
INT
075
INT
243
INT
153
INT
242
INT
INT
UDC3200 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0 = Time Simplex
1 = Current Simplex
2 = Three Position Step or
Position Proportioning
3 = Time Duplex
4 = Current Duplex
5 = Current/Time Duplex
6 = Time/Current Duplex
R/W
0 = 1 second increments
1 = 1/3 second increments
R/W
5 to 1800 seconds
0 = 1 OFF 2 OFF
R/W
1 = 1 ON 2 OFF
2 = 1 OFF 2 ON
3 = 1 ON 2 ON
0 = Full (100%)
R/W
1 = Split (50%)
0 = Disable
R/W
1 = Input 1
2 = Input 2
3 = PV
4 = Deviation
5 = Output
6 = SP
7 = LSP
8 = RSP
9 = Input Algorithm 1
0 = 4-20 mA
R/W
1 = 0-20 mA
201