Troubleshooting/Service

7.3 Power-up Tests

What happens at power-up
When power is applied, the controller will run three diagnostic tests. After these tests are
completed, "TEST DONE" is displayed.
Failsafe Failures
If one or more of these tests fail, the controller will go to the Failsafe Manual Mode, and
FAILSF will flash in the lower display and a message indicating which test failed will
appear in the lower display. Then, "DONE" will appear in the lower display.
Three Position Step test failures
For controller configured for Three Position Step Control with motor position indication
and Auto-cal has never been done, the prompt CAL MTR will appear to suggest that the
controller be calibrated. Refer to Subsection 6.4 - Three Position Step Output
Calibration.
7.4

Status Tests

Introduction
When required, the results of these tests can be checked to determine the reason the
controller has gone to Failsafe.
How to check the status tests
The procedure in Table 7-2 tells you how to display the results of the status tests.

Table 7-2 Procedure for Displaying the Status Test Results

Step
Operation
1
Select
STATUS
Set Up Group
2
Read the test
results
156
Press
Upper Display = READ
Setup
Setup
Lower Display = STATUS
You will see:
Function
Function
Function
Upper Display = NO or YES YES indicates a failure
Lower Display = FAILSAFE
Upper Display = PASS or FAIL
Function
Function
Function
Lower Display = TEST
UDC3200 Universal Digital Controller Product Manual
Result
12/04