Installation
Motor
Power
Supply
1
Alarm #2 is not available with this configuration.
Electromechanical Relays are rated at 5 amps at 120 Vac or 240 Vac
2
or 24 Vdc. Solid State Relays are rated at 1 Amp at 25 ° C and
derated linearly to 0.5 Amps at 55 ° C. Customer should size fuses
accordingly. Use Fast Blo fuses only.
See Input 2 Wi ring Diagram for Slidewire Connections.
3
Figure 2-13 Position Proportional or Three Position Step Control
Motor
Power
Supply
Alarm #2 is available with with this configuration.
1
2 Dual Electromechanical relays are rated at 2 Amps @120 Vac or 240 Vac or
30 Vdc. Customer should size fuses accordingly. Use Fast Blo fuses only.
3
See Input 2 Wiring Diagram for Slidewire Connections.
Figure 2-14 Position Proportional or Three Position Step Control
32
Open (CW)
L2/N
Close (CCW)
2
L1/Hot
Connections w/o Dual Relay Option
Close (CCW)
L2/N
Open (CW)
2
Connections with Dual Relay Option