Troubleshooting/Service

7.8 Restoring Factory Configuration

Introduction
This procedure restores the configuration of the instrument back to the Factory Settings
per Section 3.16.
ATTENTION: Restoring the factory configuration overwrites all user-entered
configuration changes. This procedure cannot be undone, it is a one-way process.
Table 7-15 explains how to restore Factory Configuration.
Step
1
Turn off the power to the instrument for at least five seconds.
2
Turn the power back on and simultaneously press the "SETUP" and
keys. This must be done while "TEST DONE" is being displayed.
If step 2 was performed correctly, the instrument will now display "UDC"
3
[Upper] "UPDATE" [Lower].
Press the Function Key. The instrument will now display "DIS" [Upper]
4
"RESTORE" [Lower].
5
Press the
"RESTORE" [Lower].
6
Press the Function Key. The instrument will now display "DOIN"
"RESTORE"
7
When the instrument finishes the restore operation, it automatically resets
itself and restarts in the product mode. The instrument configuration will
now be the same as it was when the instrument left the factory and all user-
entered configurations since that time have been overwritten.
170

Table 7-15 Restoring Factory Configuration

key. The instrument will now display "CONFIG" [Upper]
UDC3200 Universal Digital Controller Product Manual