Example Of Rack Load Calculations - HP Integrity NonStop X NS7 Planning Manual

Table of Contents

Advertisement

Table 7 Example of Rack Load Calculations
Component
c7000
enclosure
BL460c Gen8
Server Blade
D3700 SAS
disk enclosure,
containing 25
HDDs with
300GB, 6 GB
SAS protocol
per HDD
Rack-mounted
System
Console
Maintenance
switch
CLIM patch
panel
Rack
(single-phase)
Total
For a total thermal load for a system with multiple racks, add the heat outputs for all the racks in
the system.
58
NS7 System Installation Specifications
Quantity
Height (U)
Weight
(lbs)
1
10
270
4
10
25
2
3.47
38
2
2
41
2
1
6
1
1
19
1
42
338
-
-
792
Total Volt-amps (VA)
(kg)
Typical
Maximum
Power
Power
Consumption
Consumption
122
810
1250
11
920
920
17
450
710
18
204
204
3
20
20
8
-
-
153
-
-
356
2664
3514
BTU/hour
Typical
Maximum
Heat
Heat
Dissipation
Dissipation
2763
4265
3139
3139
1535
2422
696
696
68
68
-
-
-
-
9088
11998