NonStop System Console
The NonStop system console manages the system and runs maintenance and diagnostic software
in concert with the OSM console tools. An NS7 requires two system consoles running Windows
Server 2012 or Windows Server 2008 to manage the system. New system consoles arrive
preconfigured with all required HPE and third-party console software.
In a future RVU if you need to update your console software, use the HPE NonStop System
Console Installer DVD to install these updates as described in the NonStop System Console
Installer Guide.
NOTE:
Procedures related to creating or modifying the dedicated service LAN and the system
console configurations on that LAN, must be performed by an authorized Hewlett Packard
Enterprise service provider as described in the Nonstop Dedicated Service LAN Installation and
Configuration Guide for NonStop X systems.
UPS and ERM (Optional)
A rack-mounted uninterruptible power supply (UPS) is optional but recommended to provide
power during power failures when a site UPS is not available.
NOTE:
For information on using OSM to: manage a site UPS, monitor AC power, or for power
fail support, see the OSM Configuration Guide.
Hewlett Packard Enterprise supports these rack-mounted UPS modules. Both support up to two
HPE ERMs per UPS; no mixing of UPS and ERM types.
Supported UPS
Single-phase R5000
Three-phase R12000/3
More information
"Power Specifications"
UPS and ERM Checklist
UPS and ERM Checklist
Verify:
UPS and ERMs are in the lowest portion of the system to avoid tipping and stability issues.
No more than two HPE ERMs are used per UPS; no mixing of UPS or ERM types.
IMPORTANT:
Enterprise-supported UPS has been changed by your HPE service provider to an appropriate value for the
system as described in the NonStop X System Hardware Manual (only HPE service providers can refer to this
manual).
IMPORTANT:
manually reset by your HPE service provider as instructed in the NonStop X System Hardware Manual (only
HPE service providers can refer to this manual).
Your UPS configuration is supported. See
UPS Manuals
HPE UPS R5000 User Guide:
HPE UPS Network Module User Guide:
HPE 3 Phase UPS User Guide:
HPE UPS Management Module User Guide:
The manufacturing default setting ride-through time for the optional Hewlett Packard
If the optional HPE R5000 UPS has been installed, the UPS output voltage setting must be
"UPS and Data Center Power Configurations" (page
NonStop X NS7 Standard and Optional Hardware
81).