Enclosure Type
Gen9 10GbE
Networking CLIM
4F/1C
SAS disk enclosure,
empty
SAS HDD, 2.5 inches,
15k rpm
SAS, SSD, 2.5in, SC,
15k rpm
Maintenance switch
1
(Ethernet)
Rack-mounted
system console
Console keyboard
and display
1
Maintenance switch has only one plug.
Operating Temperature, Humidity, and Altitude Specifications for NS7 Systems
Specification
Temperature (rack-mounted
system console, and
maintenance switch)
Temperature (c7000,
CLIMs, and SAS disk
enclosures)
Humidity (all except c7000
enclosure)
Humidity (c7000 enclosure)
2
Altitude
1
Operating and recommended ranges see the ambient air temperature and humidity measured 19.7 in. (50 cm) from
the front of the air intake cooling vents.
2
For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet), subtract 1.5× F
(0.83× C) from the upper limit of the operating and recommended temperature ranges.
56
NS7 System Installation Specifications
Number Installed
Unit Heat
(BTU/hour, Typical
Heat Dissipation)
461
426
13
14
31
569
129
1
Operating Range
41° to 95° F (5° to 35° C)
50° to 95° F (10° to 35° C)
15% to 80%,
noncondensing
20% to 80%,
noncondensing
0 to 10,000 feet (0 to 3,048
meters)
Unit Heat (BTU/hour,
Maximum Heat
Dissipation)
631
614
23
24
51
569
129
1
Recommended Range
68° to 72° F
(20° to 25° C)
-
40% to 50%,
noncondensing
40% to 55%,
noncondensing
-
Total (BTU/hour)
Maximum Rate of Change
per Hour
9° F (5° C) Repetitive
36° F (20° C) Nonrepetitive
1.8° F (1° C) Repetitive
5.4° F (3° C) Nonrepetitive
6%, noncondensing
6%, noncondensing
-

Hide quick links: