Table 16. Gaseous contamination specifications
Gaseous contamination
Copper Coupon Corrosion
Silver Coupon Corrosion
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Expanded operating temperature

Table 17. Expanded operating temperature specifications
Expanded operating temperature
Continuous operation
≤ 1% of annual operating hours
NOTE: When operating in the expanded temperature range, the performance of the system may be
impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be
reported on the LCD panel and in the System Event Log.

Expanded operating temperature restrictions

1.
Do not perform a cold startup below 5 °C
2.
Install only 94 mm wide heat sinks
3.
Do not install more than 40 DIMMs
4.
The following do not support expanded operating temperature range:
a.
PCIe SSD
b.
Express flash
22
Specifications
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Specifications
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate continuously in temperatures as low
as 5°C and as high as 40°C.
For temperatures between 35°C and 40°C, de-rate
maximum allowable temperature by 1°C per 175 m
(1°F per 319 ft.) above 950 m (3,1171 ft.).
–5°C to 45°C at 5% to 90% RH with 29°C dew
point.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate
maximum allowable temperature by 1°C per 125 m
(1°F per 228 ft.) above 950 m (3.117 ft.).