Table 13. Maximum altitude specifications
Maximum altitude
Operating
Storage
Table 14. Operating temperature de-rating specification
Operating temperature de-rating
Up to 35°C (95°F)
35 °C to 40 °C (95 °F to 104 °F)
40 °C to 45 °C (104 °F to 113 °F)

Particulate and gaseous contamination specifications

The following table defines the limitations that will help avoid any damages to the IT equipment and/or
failure from particulates and gaseous contamination. If the levels of particulates or gaseous pollution
exceed the specified limitations and result in equipment damage or failure, you may need to rectify the
environmental conditions. Re-mediation of environmental conditions is the responsibility of the
customer.
Table 15. Particulate contamination specifications
Particulate contamination
Air Filtration
Conductive dust
Corrosive dust
Specifications
3048 m (10,000 ft)
12,000 m (39,370 ft)
Specifications
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft),
above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft),
above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft),
above 950 m (3,117 ft).
Specifications
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE: This condition applies to data center
environments only. Air filtration requirements do not
apply to IT equipment designed to be used outside a data
center, in environments such as an office or factory floor.
NOTE: Air entering the data center must have MERV11 or
MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE: This condition applies to data center and nondata
center environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE: This condition applies to data center and nondata
center environments.
21