Using Event Inputs
When multi-SP is used by
event input
4-5-3

Settings by Key Operation

4-5-4

Settings

To select set points (0/1/2/3)
Operation Procedure
64
Multi-SP can be used when the option event input unit E53-AZB is mounted
on the E5AZ/E5EZ and "number of multi-SP uses" is set to "1" or "2".
• When "number of multi-SP uses" is set to "1"
Event input 1
OFF
ON
• When "number of multi-SP uses" is set to "2"
Event input 1
OFF
ON
OFF
ON
Note Event input can be used when the option event input unit
E53-AZB is mounted in the E5AZ/E5EZ. Select event input ON/
OFF while the E5AZ/E5EZ is turned ON. Judgment of event input
ON/OFF is carried out on event inputs of 50 ms or more.
You can select set points 0 to 3 by changing the set value of the "multi-SP"
parameter. The "multi-SP" display conditions are as follows:
• When the option event input unit E53-AZB is not mounted in the E5AZ/
E5EZ, and "multi-SP" is set to "ON"
• When the option event input unit E53-AZB is mounted in the E5AZ/E5EZ,
the "number of multi-SP uses" is set to "0" and "multi-SP" is set to "ON"
The following table shows the relationship between the "multi SP" parameter
set value and the selected set point.
Multi-SP
0
1
2
3
Before you set the "number of multi SP uses," cancel protection and move to
the "advanced function setting level". For details on how to cancel protection,
refer to 4-9 Using the Key Protect Level.
Selected Set Point
Set point 0
Set point 1
Event input 2
OFF
OFF
ON
ON
Selected Set Point
Set point 0
Set point 1
Set point 2
Set point 3
Section 4-5
Selected Set Point
Set point 0
Set point 1
Set point 2
Set point 3