Omron E5AZ User Manual page 102

Digital temperature controller
Hide thumbs Also See for E5AZ:
Table of Contents

Advertisement

Operation Level
al3h
Alarm value upper limit 3
al3l
Alarm value lower limit 3
Function
Setting
See
MV monitor (OUT1)
Function
Monitor
See
These parameters independently set the alarm value upper and lower limits
alarm values when the mode for setting the upper and lower limits is selected
for alarm 3 type (initial setting level).
• This parameter sets the upper- and lower-limit values of alarm 3.
• During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the "decimal
point" parameter setting.
Setting Range
−1999 to 9999
■ Related parameters
"Input type" "Alarm 3 type" (initial setting level)
"Standby sequence reset" "Alarm 3 open in alarm" "Alarm 3 hysteresis",
"Alarm 3 latch" (advanced function setting level)
This parameter is for monitoring the manipulated variable on the control out-
put 1 side during operation.
• This parameter cannot be set.
• During standard control, the manipulated variable is monitored, and dur-
ing control output 1 and cooling control, the manipulated variable on the
heating side is monitored.
• Default is "OFF" and the manipulated variable is not displayed.
Setting Range
Standard
Heating/cooling
■ Related parameters
"Manipulated variable display" (advanced function setting level)
The control must be standard con-
trol.
Alarm 3 type must be set to upper
and lower limits, upper- and lower-
limit range, or upper- and lower-limit
alarm with standby sequence.
Unit
Default
EU
0
Manipulated variable display must be
set to "ON".
Unit
Default
0.0 to 100.0
%
0.0 to 100.0
%
Section 5-3
83