Advanced Function Setting Level
Standby sequence reset
Function
Alarm output: Condition A
Alarm output: Condition B
Setting
See
108
• This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
• Output is turned OFF when the initial setting level, communications set-
ting level, or advanced function setting level is switched to.
• Condition A:
Control started (including power ON), and set point, alarm value (alarm
value upper- and lower-limit) or input shift value (upper- and lower-limit
temperature input shift value) changed
• Condition B:
Power ON
• The following example shows the reset action when the alarm type is
lower-limit alarm with standby sequence.
Alarm point
(after change)
Alarm point
Setting Range
a: Condition A / b: Condition B
■ Related parameters
"Alarm 1 type" "Alarm 2 type" "Alarm 3 type" (initial setting level)
"Alarm 1 to 3 latch" (advanced function setting level)
The alarm 1 to 3 type must be set to
"with standby sequence."
Condition A only
SP change
Condition A only
Default
a
Section 5-6
Alarm hysteresis
: Standby sequence canceled point
: Standby sequence reset point