Setting Scaling Upper and Lower Limits (for Analog Inputs)
Operation Procedure
1,2,3...
Initial setting level
Input type
in-t
21
Scaling upper
in-h
limit
100
in-h
950
Scaling lower
in-l
limit
0
in-l
100
Decimal point
dp
0
dp
1
60
In this example, let's set the scaling upper- and lower-limits to display 0 to
50 mV as 10.0% to 95.0%.
1. Press the
key for at least three seconds to move from the "operation
level" to the "initial setting level".
2. Select "scaling upper limit" by pressing
3. Press the
or
4. Select "scaling lower limit" by pressing
5. Press the
or
6. Select the decimal point position by pressing
7. Press the
or
8. To return to the "operation level" press the
.
key to set the parameter to "950".
.
key to set the parameter to "100".
key to set the parameter to "1".
key for at least one second.
Section 4-3
.