General

1
General
PLEASE NOTE
Observe all standards and guidelines
applicable to the operation of this system
in your country.
Please note the details on the boiler type
plate. These are decisive and must be
observed.
Observe Chapter 12 "Boiler operating
conditions for countries outside the EU" on
page 61, if the boiler is used in countries
outside the European Union.
Operating conditions
Maximum flow temperature
T
/TS
max
Permissible operating pressure
PMS:
Maximum time constant
High limit safety cut-out:
Maximum time constant
Control thermostat
Type
Tab. 1
Boiler operating conditions
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
Dimension
°C
100 - 120
bar
max. 6
s
max. 40
s
max. 40
-
-
Notes - More detailed requirements
The maximum permissible flow temperature may, in compliance
with national regulations, be limited to a value within this range.
Safety limit (high limit safety cut-out).
Max. possible flow temperature = safety limit (STB) -18 K
Example:
Safety limit (STB) = 100 °C
Flow temperature = 100 °C - 18 K = 82 °C.
B
, B
11
11BS
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
1
5