Boiler operating conditions for countries outside the EU
12.8 Conditions for hydraulics and water quality
Operating conditions
Operating pressure
(overpressure)
Permissible site test pressure
Protection against over-
temperatures via "TR"
thermostat
Protection against over-
temperatures via "STB" high
limit safety cut-out
Boiler fill water
Tab. 30 Hydraulics; water quality
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
Dimension
bar
1.0 – 6.0
bar
1.0 – 6.0
°C
50 – 105
°C
100 – 120
–
–
Notes – More detailed requirements
In some areas adjustable on site from 100 to 120 °C
Only use drinking water to fill and top-up the boiler.
Observe the manual "Water treatment – requirements for
heating water". This manual is included with the technical
documentation.
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
12