Specification
Boiler
size
58 - 37
36
kW
mbar
mbar
150 - 375
35
34
Tab. 7
Nozzle pressure for LPG P subject to the supply pressure
Boiler
size
58 - 37
36
kW
mbar
mbar
150 - 375
31.5
31.5
Tab. 8
Nozzle pressure for LPG B/P subject to the supply pressure
Boiler size
Natural gas
kW
150
175
200
225
250
275
300
325
350
375
Tab. 9
Gas throughput
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
35
34
mbar
mbar
33
32
35
34
mbar
mbar
31.5
31.5
Natural gas
H
(G20)
m³/h
16.2
19.0
21.7
24.4
27.0
29.7
32.4
35.1
37.8
40.5
Nozzle pressure
LPG
Propane
P (G 31)
Supply pressure
(Flow pressure)
33
32
31
mbar
mbar
mbar
31
30
29
Nozzle pressure
LPG
Butane/propane mixtures
B/P (G 30)
Supply pressure
(Flow pressure)
33
32
31
mbar
mbar
mbar
31
30
29
Gas throughput
L
Propane
(G25)
m³/h
18.9
22.0
25.2
28.3
31.4
34.5
37.7
40.8
44.0
47.1
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
30
29
mbar
mbar
mbar
28
27
30
29
mbar
mbar
mbar
28
27
LPG
(G31)
kg/h
12.6
14.7
16.8
18.9
20.9
23.0
25.1
27.2
29.3
31.4
4
28
27
mbar
26
25
28
27
mbar
26
25
LPG
B/P
(G30)
kg/h
12.8
14.9
17.0
19.2
21.2
23.3
25.5
27.6
29.7
31.9