RWF40
Power regulator RWF40 electrical
connection
Key to layout
CMV
Motor contactor
LAL 1.25 Control box
FR
Photocell
MB
Terminal strip
MV
Fan motor
PO
Oil pressure switch
RT
Thermal cut-out
S1
Power switch for different operations:
MAN = manual
AUT = automatic
OFF = off
S2
Button for:
– power reduction
+ power increase
SM
Servomotor
TA
Ignition transformer
TB
Burner ground (earth) connection
VM
Delivery pump valve
VS
Delivery pump valve (safety valve)
VS1
Safety valve on return
VU
Valve on nozzle return
BT
Temperature probe
BP
Pressure probe
IN
Manual burner stop switch
MB
Terminal strip
RS
Remote lock-out reset button (if present)
S
Remote lock-out signal
TL
Limit control device system: this shuts down the burn-
er when the boiler temperature or pressure exceeds
the setpoint value.
TR
High-low mode control device system: this controls
operating stages 1
The TR load control is not required when the regulator
RWF40 is connected as its function is performed by
the regulator RWF40 itself.
TS
Safety control device system: this operates when TL
is faulty.
Appendix - Electrical panel layout
st
nd
and 2
.
D1910
33
GB
Fig. 3
20033337