BURNER DESCRIPTION (A) 1 Ignition electrodes 2 Combustion head 3 Screw for combustion head adjustment 4 Screw for fixing fan to flange 5 Slide bars for opening the burner and inspecting the combustion head 6 Safety solenoid valve 7 Pump 8 Air inlet to fan 9 Air damper 10 Hydraulic cylinder for regulation of the air damper...
FIRING RATE (A) The RL 70 - 100 - 130 Model burners can work in two ways: Low and High fire. LOW FIRE DELIVERY must be selected within area A of the adjacent diagrams. HIGH FIRE DELIVERY must be selected within area B (and C for model RL 130).
INSTALLATION inch BOILER PLATE (A) Drill the combustion chamber mounting plate as shown RL 70 “ “ - 12 “ 1 / 2 9 / 32 27 / 32 13 / 16 in (A). The position of the threaded holes can be RL 100 “...
(F) is level with the front surface of flange 5)(E). Example: The RL 70 Model with two 6.00 GPH nozzles and 174 PSI pump pressure. Find the delivery of the two 6.00 GPH nozzles in table (D), page 7: 8.17 + 8.17 = 16.34 GPH.
HYDRAULIC SYSTEM FUEL SUPPLY Double-pipe circuit (A) The burner is equipped with a self-priming pump which is capable of feeding itself within the limits listed in the table at the left. The tank higer than the burner A The distance "P" must not exceed 32 ft in order to avoid subjecting the pump's seal to excessive strain;...
- in rh direction (- sign) the opening is reduced - in lh direction (+ sign) the opening increases. Example RL 70 - Low fire nozzle 6.00 GPH: 2.3 (A) notch aligned with index 1)(A). When the adjustment is done lock the hex element 2)(B) with the ring nut 1).
FINAL CHECKS • Obscure the photocell and switch on the control devic- es: the burner should start and then lock-out about 5 s after opening of the low fire nozzle operation valve. • Illuminate the photocell and switch on the control cir- cuit: the burner should go into lock-out .
BURNER OPERATION BURNER STARTING (A) Operating control closes. The motor starts and the ignition transformer is con- nected. The pump 3) sucks the fuel from the tank through the piping 1) and the filter 2) and pumps it under pressure to delivery.
PROCEDURE TO REFER BURNER OPERATING CONDITION IN HIGH ALTITUDE PLANTS Find the corrected burner capacity for the plant’s altitude in chart 1 and the corrected pressure in chart 2. Check in the firing rate graph of the burner (page 6), if the working point defined by the values above is within the range limits. If not, higher burner size is needed.
FLAME SIGNAL MEASUREMENT (A) LAL2... Sub-base Min value for a good signal: 8 μA. If the value is lower, it can be due to: • Worn photocell; • Low current; • Bad set up of the burner. In order to measure the current, use a microammeter of 100 A c.c., connected to the scanner, as in the dia- gram.
BURNER FAULTS SYMBOL (1) FAULT PROBABLE CAUSE SUGGESTED REMEDY The burner does not start - A limit or safety control device is open ....Adjust or replace - Control box lock-out .
Motor connection at 208-230 or 460V WARNING: the motors, manufactured for 208-230/460 IE2/Epact voltage, have a different connection than IE1 motors, no more star/delta but star/ double star. Please, pay attention to the indications in case of modification of voltage, maintenance, or substitution. IE2/Epact S8380 S8379...
For the calibration, refer to the table below. To reset, in the case of an intervention of the thermal relay, press the button 1) of (A). D8267 IE 1 RL 70 RL 100 RL 130 208 - 230 V 460 V...
13 of control box. D2872 LAYOUT (A) - Air pressure switch Burners RL 70 - 100 - 130 - Ignition transformer The flame safeguard is on burner mounted - Burner ground (earth) connection - Low fire solenoid valve...
Page 21
• The RL 70 - 100 - 130 burners have been type-approved for intermittent operation. This means they should compulsorily be stopped at least once every 24 hours to enable the control box to perform checks of its own efficiency at start-up.
BURNER START UP REPORT Model number: Serial number: Project name: Start-up date: Installing contractor: Phone number: GAS OPERATION Gas Supply Pressure: : Low Fire High Fire Main Power Supply: : Low Fire High Fire Control Power Supply: CO: Low Fire High Fire Burner Firing Rate: : Low Fire...