Installation, use and maintenance instructions
Light oil burners
Low - High Operation
CODE
C9514200 (3475070)
C9514201 (3475075)
C9515200 (3475270)
C9515201 (3475275)
C9516200 (3475470)
C9516201 (3475475)
MODEL
RL 70
RL 70
RL 100
RL 100
RL 130
RL 130
TYPE
660T70
660T70
661T70
661T70
662T70
662T70
C6505052 - 2916049 (6) - 06/2011

Advertisement

Table of Contents
loading

Summary of Contents for Riello RL 70

  • Page 1 Installation, use and maintenance instructions Light oil burners Low - High Operation CODE MODEL TYPE C9514200 (3475070) RL 70 660T70 C9514201 (3475075) RL 70 660T70 C9515200 (3475270) RL 100 661T70 C9515201 (3475275) RL 100 661T70 C9516200 (3475470) RL 130 662T70...
  • Page 3: Table Of Contents

    CONTENTS WARNING TECHNICAL DATA ......page 3 Do not store flammable or hazardous materials in the vicinity of Burner models designations .
  • Page 4: Technical Data

    TECHNICAL DATA MODEL RL 70 RL 100 RL 130 Output High fire MBtu/hr 1792 - 3136 2688 - 4480 3584 - 5824 Delivery 12.8 - 22.4 19.2 - 32 25.6 - 41.6 Low fire MBtu/hr 966 - 1792 1344 - 2688 1834 - 3584 6.9 - 12.8...
  • Page 5: Burner Models Designations

    L1 = Length obtainable with the kit COD. 3010253 L = 9 27 / 32 “ L1 = 15 5 / 32 “ • RL 70 COD. 3010254 L = 9 “ L1 = 15 “ • RL 100 27 / 32 5 / 32 COD.
  • Page 6: Burner Description

    BURNER DESCRIPTION (A) 1 Ignition electrodes 2 Combustion head 3 Screw for combustion head adjustment 4 Screw for fixing fan to flange 5 Slide bars for opening the burner and inspecting the combustion head 6 Safety solenoid valve 7 Pump 8 Air inlet to fan 9 Air damper 10 Hydraulic cylinder for regulation of the air damper...
  • Page 7: Firing Rate

    FIRING RATE (A) The RL 70 - 100 - 130 Model burners can work in two ways: Low and High fire. LOW FIRE DELIVERY must be selected within area A of the adjacent diagrams. HIGH FIRE DELIVERY must be selected within area B (and C for model RL 130).
  • Page 8: Installation

    INSTALLATION inch BOILER PLATE (A) Drill the combustion chamber mounting plate as shown RL 70 “ “ - 12 “ 1 / 2 9 / 32 27 / 32 13 / 16 in (A). The position of the threaded holes can be RL 100 “...
  • Page 9: Nozzle Assembly

    (F) is level with the front surface of flange 5)(E). Example: The RL 70 Model with two 6.00 GPH nozzles and 174 PSI pump pressure. Find the delivery of the two 6.00 GPH nozzles in table (D), page 7: 8.17 + 8.17 = 16.34 GPH.
  • Page 10: Fuel Supply

    HYDRAULIC SYSTEM FUEL SUPPLY Double-pipe circuit (A) The burner is equipped with a self-priming pump which is capable of feeding itself within the limits listed in the table at the left. The tank higer than the burner A The distance "P" must not exceed 32 ft in order to avoid subjecting the pump's seal to excessive strain;...
  • Page 11: Pump

    PUMP (A) 1 - Suction 1/4” NPT 2 - Return 1/4” NPT 3 - Pressure gauge attachment G 1/8 4 - Vacuum gauge attachment G 1/8 5 - Pressure adjustment screw D2329 6 - Screw for by-pass A - Min. delivery rate at 174 PSI pressure B - Delivery pressure range C - Max.
  • Page 12: Burner Calibration

    - in rh direction (- sign) the opening is reduced - in lh direction (+ sign) the opening increases. Example RL 70 - Low fire nozzle 6.00 GPH: 2.3 (A) notch aligned with index 1)(A). When the adjustment is done lock the hex element 2)(B) with the ring nut 1).
  • Page 13: Final Checks

    FINAL CHECKS • Obscure the photocell and switch on the control devic- es: the burner should start and then lock-out about 5 s after opening of the low fire nozzle operation valve. • Illuminate the photocell and switch on the control cir- cuit: the burner should go into lock-out .
  • Page 14: Burner Operation

    BURNER OPERATION BURNER STARTING (A) Operating control closes. The motor starts and the ignition transformer is con- nected. The pump 3) sucks the fuel from the tank through the piping 1) and the filter 2) and pumps it under pressure to delivery.
  • Page 15: Procedure To Refer Burner Operating Condition In High Altitude Plants

    PROCEDURE TO REFER BURNER OPERATING CONDITION IN HIGH ALTITUDE PLANTS Find the corrected burner capacity for the plant’s altitude in chart 1 and the corrected pressure in chart 2. Check in the firing rate graph of the burner (page 6), if the working point defined by the values above is within the range limits. If not, higher burner size is needed.
  • Page 16: Flame Signal Measurements

    FLAME SIGNAL MEASUREMENT (A) LAL2... Sub-base Min value for a good signal: 8 μA. If the value is lower, it can be due to: • Worn photocell; • Low current; • Bad set up of the burner. In order to measure the current, use a microammeter of 100 A c.c., connected to the scanner, as in the dia- gram.
  • Page 17: Burner Faults

    BURNER FAULTS SYMBOL (1) FAULT PROBABLE CAUSE SUGGESTED REMEDY The burner does not start - A limit or safety control device is open ....Adjust or replace - Control box lock-out .
  • Page 18: Motor Connection At 208-230 Or 460V

    Motor connection at 208-230 or 460V WARNING: the motors, manufactured for 208-230/460 IE2/Epact voltage, have a different connection than IE1 motors, no more star/delta but star/ double star. Please, pay attention to the indications in case of modification of voltage, maintenance, or substitution. IE2/Epact S8380 S8379...
  • Page 19: Calibration Of The Thermal Relay

    For the calibration, refer to the table below. To reset, in the case of an intervention of the thermal relay, press the button 1) of (A). D8267 IE 1 RL 70 RL 100 RL 130 208 - 230 V 460 V...
  • Page 20: Factory Wiring Diagram

    13 of control box. D2872 LAYOUT (A) - Air pressure switch Burners RL 70 - 100 - 130 - Ignition transformer The flame safeguard is on burner mounted - Burner ground (earth) connection - Low fire solenoid valve...
  • Page 21 • The RL 70 - 100 - 130 burners have been type-approved for intermittent operation. This means they should compulsorily be stopped at least once every 24 hours to enable the control box to perform checks of its own efficiency at start-up.
  • Page 22: Burner Start Up Report

    BURNER START UP REPORT Model number: Serial number: Project name: Start-up date: Installing contractor: Phone number: GAS OPERATION Gas Supply Pressure: : Low Fire High Fire Main Power Supply: : Low Fire High Fire Control Power Supply: CO: Low Fire High Fire Burner Firing Rate: : Low Fire...
  • Page 23: Spare Parts List

    SPARE PARTS LIST...
  • Page 24 BURNER SERIAL NUMBER COD. DESCRIPTION DESCRIZIONE MATRICOLA BRUCIATORE • • • • • • 3003948 AIR DAMPER ASSEMBLY GRUPPO SERRANDA • • • • • • 3003949 GRID PROTEZIONE • • • • • • C5360001 3012950 CONTROL BOX BASE ZOCCOLO •...
  • Page 25 BURNER SERIAL NUMBER COD. DESCRIPTION DESCRIZIONE MATRICOLA BRUCIATORE • 3013060 MOTOR 575V MOTORE 575V • 3013061 MOTOR 575V MOTORE 575V • • • • • • 3003969 HALF-SHELL GUSCIO • • • • • • 3003481 SCREW VITE • • • • • • 3003970 PERNO •...
  • Page 26 BURNER SERIAL NUMBER COD. DESCRIPTION DESCRIZIONE MATRICOLA BRUCIATORE • • • • • • 3003997 VALVE ASSEMBLY GRUPPO VALVOLE • • • • • • 3013525 CONNECTOR RACCORDO • • • • • • 3006722 CONNECTOR RACCORDO • • • • • • 3013523 PUMP POMPA...

This manual is also suitable for:

Rl 100Rl 130

Table of Contents