10 - INSTALLATION - Vent and combustion air
A = Flue exhaust connection
B = Combustion air intake connection
C = Fixing clamp
D = Stainless steel elbow
E = Stainless steel adaptor
F = Stainless steel extension
G = Air intake pipe
Figure 10-9 Stainless Steel Venting connection
10.8 - Stainless
steel vent piping
materials
WARNING!!!
materials, vent systems, and
terminations listed in Tables
10-1 and 10-2. DO NOT mix
vent systems of different types
or manufacturers, unless
listed in this manual. Failure to
comply could result in severe
personal injury, death, or
substantial property damage.
WARNING!!!
Check stamped
arrow on boiler adapter for the
correct side of fl ue exhaust and
air intake. Failure to follow this
warning could result in excessive
levels of carbon monoxide or a
fi re, which can result in severe
personal injury or death!
38
WARNING!!!
appliance requires a special
venting system. The fi eld
provided vent fi ttings must
be connected to the boiler
following Section 10.8.1.
Use only the
Failure to follow this warning
could result in fi re, personal
injury, or death.
WARNING!!!
installation of Stainless steel
systems may result in injury or
death.
WARNING!!!
water-based lubricants on joints.
Never use hydrocarbons-based
lubricants because they would
destroy gaskets. Failure to
follow this warning could result
in excessive levels of carbon
monoxide, which can result
in severe personal injury or
death!
NOTICE Installation must comply with
local requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
For installation in Canada, vent pipe
system must be certifi ed to ULC-S636
(see Table 10-1).
NOTICE All vent pipes connections
must be secured following manufacturer
instruction, properly supported, and the
exhaust must be pitched a minimum of
a 1/4 inch per foot back to the boiler (to
allow drainage of condensate).
NOTICE Installation of a stainless
steel vent system should adhere to
the stainless steel vent manufacturer's
installation instructions supplied with
the vent system.
NOTICE The installer must use a
specifi c vent starter adapter at the
fl ue collar connection, supplied by the
vent manufacturer to adapt to its vent
system. See Table 10-2 for approved
vent adapters.