Display In Energy Saving Mode; Users' Menu - Slant/Fin VSL-160B Installation Instructions Manual

Direct-vent sealed combustion condensing boiler
Table of Contents

Advertisement

13 - USE
13.15 - Display
in energy saving
mode
If desired, the display, item "1" and
"2" in Figure 13-1, can be switched
permanently off, with the exception
of when it displays errors or settings.
To switch the display off, access the
"Installers' Menu", in section 13.17
and set the
parameter at a value
other than zero. Keep in mind that
each value will correspond to a delay
in minutes until the display goes into
Energy Saving mode.
PARAMETER
DESCRIPTION
Adjustment of the curve angel as shown in
Figure 13-2 when outdoor reset is active per
section 13.9.
Adjustment of the "Minimum heating
temperature" as shown in Figure 13-2 when
outdoor reset is active per section 13.9.
Adjustment of the "Maximum heating
temperature" as shown in Figure 13-2 when
outdoor reset is active per section 13.9.
Adjustment of the parallel shift of the curve as
shown in Figure 13-3 when outdoor reset is
active per section 13.9.
Display of the calculated heating temperature
when outdoor reset is active per section 13.9,
or display of the temperature set by knob "7"
shown in Figure 13-1.
Display of the domestic hot water temperature
when set by knob "11" shown in Figure 13-1.
Display of last error code registered, Section
13.18.2
Display of last lockout occurred, Section
13.18.1
13.16 - "Users'
menu"
When entering the "Users' menu", the
display, item "1" in Figure 13-1, will
start blinking indicating that a change
of mode has taken place. To access
the "Users' menu" (see also Section
17 to better understand the several
menus):
1. press the
button for 2
seconds until the display starts
blinking;
2. press and release the
several times until the desired
parameter is displayed;
3. use the
or
change the value of the selected
parameter;
75
4. press
change before going to the next
parameter.
When the last parameter has been
reached and the
pressed, the display will stop blinking
indicating exit from the menu.
NOTE: If no key is pressed for
more than 60 seconds, the control
automatically exits the "Users' menu".
Any parameter change not saved
button
using the
The table below lists each "Users'
menu" parameter, what it affects and
keys, to
its adjustment range.
INFORMATION ON DISPLAY ITEM "2" of Figure 13-1
Setting range: 0,1 to 5,0
Setting range: see section 13.10.3
Setting range: see section 13.10.3
The adjustment is made by turning knob "7" shown
in Figure 13-1. The selected curve can be shifted
up or down by 36 °F (20 °C).
Temperature display only, with a range between 68
°F (20 °C) and 189 °F (87 °C).
Temperature display only with a range between 104
°F (40 °C) and 158 °F (70 °C), see section 13.7.
Error code display per section 13.18.2
Lockout code per section 13.18.1
to save the parameter
button
button, will be lost.