GAS-FIRED CAST IRON BOILERS FOR NATURAL AND L.P . PROPANE GASES
GALAXY
INSTALLATION AND OPERATING INSTRUCTIONS
CONTENTS ...........................................................................PAGE
Dimensions............................ .......................................................2
Boiler Location........................................ ................................ 3
Boiler Foundation.................................... ............................... 3
Chimney Requirements............................. ............................. 3
Minimum Clearance................................................................. 3-4
Vent Piping.............................................................................. 4
Gas Piping............................................. ...................................... 4
Boiler Room Air Supply and Ventilation.................................. 5
Draft Hood Installation.............................. .............................. 5
Piping at Boiler-Water Boilers................... ........................... 5
Steam Controls Assembly and Installation............................. 6
Piping a Steam Boiler ......................................................... 6, 7
Vent Damper.................................................................. 7, 8, 12
Electrical Controls and Wiring.................... ............................ 9
Pump or Valve Zoning-Water Boilers.............. .................. 10-11
Boiler Water Temperature Control .......................................12-13
Filling and Venting Water Systems.............. ......................... 14
Initial Start, Safety and Lighting Instructions... ..................... 15
Burner Adjustment, Checking Gas Input.............................. 15
Controls, Safety Check ......................................................... 17
Low Water Cut-off Check-Out .................................................... 17
Pressure Control Check-Out ..................................................... 17
Blowing Off a Steam Boiler........................ ................................ 17
Care and Maintenance.................................. ............................ 18
Safety Check for Control System................ ......................... 18
Protection From Freezing.......................... ........................... 18
Water Treatment.....................................................................18
Sequence of Operations............................................................ 21
Troubleshooting Guide ...............................................................22
Appendix A & B.......................................................................... 23
Appendix C, D & E......................................................................24
Heating Contractor
Address
Phone Number
HOT WATER-Models GG-75H through GG-399H
LOW PRESSURE STEAM AND HOT WATER- Models GXH-105 through GXH-300H
IMPORTANT
READ ALL OF THE FOLLOWING WARNINGS AND
STATEMENTS BEFORE READING THE INSTALLATION
INSTRUCTIONS.
WARNING
SEE "WARNING" ON PAGE 3
FOR LIQUEFIED PETROLEUM (L.P .)
PROPANE GAS-FIRED BOILERS
The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the National Fuel Gas Code, ANSI Z223.1-
latest edition or
CSA B 149.1 latest edition for natural gas
and propane
. The installation must also conform to the
additional requirements in this Slant/Fin Instruction Book.
In addition, where required by the authority having juris dic -
tion, the installation must conform to American Society of
Mechanical Engineers Safety Code for Controls and Safety
Devices for Automatically Fired Boilers, No. CSD-1 or
149.1 latest edition for natural gas and propane
any conflict in the above requirements, then the more
stringent requirement will apply.
This manual must be left with owner and should be hung on
or adjacent to the boiler for reference.
WARNING
This boiler, gas piping and accessories must be installed,
connected, serviced and repaired by a trained, experienced
service technician, familiar with all precautions required for
gas-fired equipment and licensed or otherwise qualified, in
compliance with the authority having jurisdiction.
Boiler Model Number
Boiler Serial Number
Installation Date
Printed in Canada 0713
Part No. 41-0549
CSA B
. If there is
PUBLICATION GG-41
Revision B

Advertisement

Table of Contents
loading

Summary of Contents for Slant/Fin Galaxy

  • Page 1: Table Of Contents

    . The installation must also conform to the Vent Damper..............7, 8, 12 additional requirements in this Slant/Fin Instruction Book. Electrical Controls and Wiring..........9 Pump or Valve Zoning—Water Boilers........ 10–11 In addition, where required by the authority having juris dic - Boiler Water Temperature Control ........12–13...
  • Page 2 GALAXY Pressure Relief Valve 3/4" 1/2" Vent Tapping Alternate 1-1/2" return (except GG-75 thru GG-175 FRONT VIEW RIGHT SIDE RIGHT SIDE RIGHT SIDE All GG and GXH GG / GXH-PT GXH-PZT-PPZT GXH-PZ GG SERIES HOT WATER BOILERS—DIMENSIONS IN MM FOLLOWED BY INCHES...
  • Page 3: Installation Requirements

    GALAXY INSTALLATION REQUIREMENTS CHIMNEY REQUIREMENTS— A. Galaxy boilers may be vented into a masonry vitreous tile- The installation must conform to the requirements of the author- lined chimney UL listed or Type “B” Venting system NOT ity having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition or...
  • Page 4: Vent Piping

    GALAXY GAS PIPING— GALAXY GXH SERIES A. Local installation codes apply. The pipe joint compound used on threads must be resistant to the action of liquefied petroleum gases. MODELS GXH-105 MODELS GXH-210 TO B. The gas supply line to the boiler should be run directly from the THROUGH GXH-190 GXH-300H.
  • Page 5: Boiler Room Air Supply And Ventilation

    GALAXY BOILER ROOM AIR SUPPLY AND VENTILATION 1100 mm per kW (1 square inch per 2000 BTUH) of total An ample supply of air is required to obtain combustion and ven- appliances’ input. tilation. ALL AIR COMES FROM OUTSIDE, directly through wall C.
  • Page 6: Steam Controls Assembly And Installation

    INSTRUCTIONS Pocketing of condensate and the inability to maintain the cor- Steam kit components for Galaxy packaged models are packed rect minimum height between the steam supply main and the as follows: water level in the boiler are but a few of the many conditions A.
  • Page 7: Vent Damper

    Pipe sizes shown above for Hartford Loop are recommended by Once you have begun vent damper installation procedure, DO Slant/Fin. However, certain local codes may require larger pipe sizes. NOT restore electric power and gas supply until installation and Consult with local authorities.
  • Page 8 4. All Slant/Fin Galaxy steam boilers equipped with intermit- tent pilot ignition systems are factory wired except for the wires to the low water cut-off and pressure cut-off. Wire...
  • Page 9 GALAXY ELECTRICAL WIRING 2. Power Connection DANGER:Before wiring, always turn off electric power supply, Connect hot and neutral to black and white wires inside junction box at otherwise shock or death can result. the boiler (See figure 8). 1. Power Supply Connect ground wire to ground screw inside junction box.
  • Page 10 GALAXY Figure 9. Multizoning of Galaxy boilers pump zoning system using R845A relay. Figure 10. Multizoning of Galaxy boiler-2 zone system pump zoning system using R882A/B relays.
  • Page 11 GALAXY Figure 10a. Multizoning of Galaxy boilers zone valve system using R8043E/F zone valves.
  • Page 12 GALAXY I. BOILERS EQUIPPED WITH HYDROSTAT CONTROL Dynamic Diagnostic LEDs and c i t SETTING THE CONTROL Test Button Display Water Temperature and Real Time and R and R Jumper Verification of Setting c i f of f Adjustments. Economy Dial...
  • Page 13 GALAXY LED LEGEND and TEST/SETTINGS BUTTON water reaches the target temperature, the TEMP ACTIVE Indicates that the LED illuminates and the burner will shut Fuel Smart HydroStat control is powered down. The boiler water will continue to cir- and that the temperature function is culate and heat the house as long as the active.
  • Page 14: Operating Instructions

    GALAXY FIGURE 12 FIGURE 11 CAUTION DO NOT USE ONE VENT DAMPER TO CONTROL TWO HEATING APPLIANCES DAMPER DAMPER DANGEROUS CAUTION TO PREVENT INTERFERENCE WITH DAMPER VANE HEATING HEATING HEATING HEATING MOVEMENT, SCREWS OR POP RIVETS MUST NOT BE APPLIANCE...
  • Page 15 1. Set the thermostat to lowest setting. the Galaxy Series boilers under the ANSI Z21.13b-1994 or 2. Turn off all electric power to the appliance if service is to be CSA B 149.1 latest edition for natural gas and propane.
  • Page 16 (For 1050 Btu/cu.ft. gas, this becomes: Input = cu. ft. metered in 3 minutes × 1050 × 20) 5. The higher heating value* of gas varies substantially for different localities. Consult with Slant/Fin’s Technical Service Dept. for re-orificing procedures if any of the following apply: C.Main Burner Ignition Check-out and Pilot Adjustment...
  • Page 17: Controls, Safety Check

    1. While boiler is running, drain down boiler water slowly Steam Controls Installation Instructions through Boiler Drain Cock shown on page 7, just until light A. Steam kit components for Galaxy packaged models are goes on. Boiler should shut down 90 seconds after light packed as follows: goes on.
  • Page 18 FIGURE A FIGURE B Right side view of Galaxy models that are NOT equipped Left side view of Galaxy models that are equipped with or have pro- with or DO NOT have provisions for tankless heaters. visions for tankless heaters.
  • Page 19: Care And Maintenance

    GALAXY Remove draft hood, jacket top and flue cover. CARE AND MAINTENANCE Use wire brush to clean flueways. This section must be brought to the attention of the owner by Replace flue cover and re-seal with furnace cement. the installer so that the owner can make the necessary arrange-...
  • Page 20: Water Treatment

    GALAXY WATER TREATMENT: A good water treatment program will not only extend the useful life of this boiler but it will also save much of the time and expense of repairs made necessary by preventable occurrences. A reputable water treatment company should be consulted to evaluate and determine the best overall treatment program for your boiler equipment.
  • Page 21 GALAXY SEQUENCE OF OPERATION FOR GALAXY BOILERS EQUIPPED WITH HONEYWELL INTERMITTENT PILOT IGNITION SYSTEM (IID) THERMOSTAT CALLS FOR LOW LIMIT (FOR TANKLESS COIL) HEAT CALLS FOR HOT WATER HIGH LIMIT CONTACTS CLOSED? NO FURTHER LOW WATER CUT OFF (WHEN USED) CONTACTS CLOSED?
  • Page 22 GALAXY TROUBLE SHOOTING BURNERS FAIL TO OPERATE CAUSE REMEDY 1. Safety pilot out, or flame too low. 1. Check, clean, re-light. See instructions. 2. Gas supply valve shut off. 2. Open gas valve(s). 3. Electric switch open. 3. Close switch.
  • Page 23 GALAXY APPENDIX A Removal of Existing Boiler from Common Vent System "At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation."...
  • Page 24 Use of Non-oxygen Diffusion Barrier Underfloor Tubing The boiler warranty does not cover leaks resulting from with a heat exchanger, Slant/Fin recommends the use of corrosion caused by the use of underfloor plastic tubing underfloor plastic tubing with an oxygen diffusion barrier.