Slant/Fin Jaguar Caravan J-390C Series Application Manual

Slant/Fin Jaguar Caravan J-390C Series Application Manual

Hot water/gas multiple and cascading boilers

Advertisement

Quick Links

Guidelines for the design, purchase and installation of Slant/Fin Jaguar J-390C Caravan gas-fired, hot water multiple boiler systems.
CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . .2
Boiler room design & layout . . . . . . . . . . . . . . . . . . . . . .4
Fresh air and contamination prevention . . . . . . . . . . . . .6
Piping and Wiring Flow
Boiler room air supply & ventilation . . . . . . . . . . . . . . . . .6
Venting requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Water piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Condensate removal . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Gas line sizing and layout . . . . . . . . . . . . . . . . . . . . . . .16
Jaguar Multiple Boiler System Control . . . . . . . . . . . . .18
Cascading - Jaguar link method and wiring . . . . . . . . .19
Reset curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
External signal & energy management (Tekmar 275) . . . . . . .28
Hybrid Boiler System . . . . . . . . . . . . . . . . . . . . . . . . . . .34
CODES AND STANDARDS
All Caravan installations must comply to local codes or, in the
absence of local codes, to the National Fuel Gas Code, ANSI,
Z223.1-latest edition.
In addition where required by the authority having jurisdiction, the
installation must conform to American Society of Mechanical
Engineers Safety Codes for controls and safety devices for
automatically fired boilers, No. CSD-1. The installation must also
conform to the additional requirements of Slant/Fin Instruction Book
publication no. J-40 latest edition.
All electrical wiring is to be done in accordance with the National
Electrical Code ANSI/NFPA No. 70-latest edition and all local electri-
cal codes. The unit must be electrically grounded if an external
power source is used.
In Canada, the installation must be in accordance with standards
CGA B149.1 and B149.2, installation codes for gas burning
appliances and equipment and/or local codes. All electrical
connections are to be made in accordance with Standard C.S.A.
C22.1 Canadian Electrical Code Part 1 and/or local codes.
HOT WATER/GAS
MULTIPLE AND
CASCADING BOILERS
®
APPLICATION GUIDE
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a system can
cause scaling and leave deposits in the boiler and the surrounding
pipes. This will lead to inefficient boiler operation and breakdown.
Fresh water will enter the system as a result of hidden leaks such
as may occur in underground piping. Relief valves should be piped
to a location that shows visible signs of relief.
Process applications that use fresh water, require the use of heat
exchangers. Any process application that results in introduction of
fresh water into a boiler can cause scaling with deposits forming in
the boiler and surrounding piping. This will damage the boiler.
Introduction of fresh water from leaks will cause similar damage.
In some areas it may be necessary to use a feed water treatment to
control the corrosive makeup of the feed water. Check with the local
authority, to determine if the feed water will need a conditioning
treatment before being supplied to the boiler.
Printed in the U.S.A. 711 Publication No. CJ-10-HWG
www.slantfin.com

Advertisement

Table of Contents
loading

Summary of Contents for Slant/Fin Jaguar Caravan J-390C Series

  • Page 1: Table Of Contents

    ® APPLICATION GUIDE Guidelines for the design, purchase and installation of Slant/Fin Jaguar J-390C Caravan gas-fired, hot water multiple boiler systems. CONTENTS Introduction ........2 Ratings and Dimensions .
  • Page 2: Introduction

    Slant/Fin Sales Representative or Slant/Fin Technical Services. there is a 12" minimum distance between them. Slant/Fin may be found on the web at www.slantfin.com There are two methods available to control J-390C Caravan boilers: This application manual is intended to provide the piping and control 1.
  • Page 3 ‘’ ‘’ ‘’ ‘’ ‘’ ‘’ ‘’ ** “L” Dimensions and spacing between boilers are for Slant/Fin headers. ‘’ ‘’ † Based on 150 BTUH per square foot E.D.R. at 170˚F water temperature. No. of Boilers Model No. “L” inches...
  • Page 4: Boiler Room Design & Layout

    Boilers can be installed in MINIMUM ALCOVE AND CLOSET CLEARANCE line, back to back, at angles or in multiple rows. Layout is flexible. Figure 2 gives a typical layout using Slant/Fin Headers. For Combustible Recommended...
  • Page 5 Jaguar Caravan Multiple and Cascading Boilers Figure 2. Typical layout of 3 Jaguar Boilers using Slant/Fin Headers (Minimum Clearance)
  • Page 6: Fresh Air And Contamination Prevention

    Jaguar Caravan Multiple and Cascading Boilers 4. FRESH AIR AND CONTAMINATION PREVENTION 5. BOILER ROOM AIR SUPPLY AND VENTILATION The combustion air supply must not be susceptible to contamina- An ample supply of air is required for combustion and ventilation. tion sources, whether the combustion air comes from the interior When buildings are insulated, caulked and weather-stripped, now or exterior of the building.
  • Page 7: Venting Requirements

    Jaguar Caravan Multiple and Cascading Boilers 2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monox- 6. VENTING REQUIREMENTS ide detector as required in accordance with the above provisions shall comply The Jaguar J-390C is a sealed combustion type boiler, it may be with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
  • Page 8 • See figure 4, 5 & 6 for direct vent side wall venting using the braces can be affixed. Slant/Fin vent/air intake termination. 9. Minimum clearances of vent pipes from combustible constructions • See figure 6 for direct vent side wall venting with close spacing.
  • Page 9 Jaguar Caravan Multiple and Cascading Boilers Wall opening for Slant/Fin vent air intake termination Height - 5 3/4" Width - 12 3/4” Wall thickness - 3” to 14” Figure 4.
  • Page 10 Jaguar Caravan Multiple and Cascading Boilers Figure 5.
  • Page 11 Jaguar Caravan Multiple and Cascading Boilers Figure 6. Alternative multiple side wall air intake & exhaust venting. Note: • Air intake opening must be 12 inches minimum above snow line or grade if it does not snow in area boilers are located. •...
  • Page 12 Jaguar Caravan Multiple and Cascading Boilers Figure 7.
  • Page 13 Jaguar Caravan Multiple and Cascading Boilers Figure 8. Direct Venting and Air Intake Through a Roof. ** Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to. This height should be used as the snow line.
  • Page 14: Water Piping

    System may be piped flow rate. A primary loop circulator is factory supplied with each 23.5 30˚ 11.5 using Slant/Fin supplied Jaguar boiler, this circulator should be used in the boilers primary 20.0 35˚ headers or by using field loop. Listed below is a chart listing the Jaguar boiler’s pressure...
  • Page 15 Jaguar Caravan Multiple and Cascading Boilers Figure 10. shows typical field piped primary loops for Jaguar Multiple boiler systems. Each Jaguar boiler shall be installed with a manual reset Hi Limit and a Manual Reset Low Water Cutoff being located on the boiler side of any shut off valves and check valves.
  • Page 16 Jaguar Caravan Multiple and Cascading Boilers...
  • Page 17: Gas Line Sizing And Layout

    Jaguar Caravan Multiple and Cascading Boilers 9. GAS LINE SIZING AND LAYOUT GAS PIPING Gas main sizing This section contains sizing and construction recommendations To determine the correct pipe diameter for the gas main serving a for fuel supply piping to Caravan gas-fired modular boiler sys- specific Caravan system, proceed as follows: tems.
  • Page 18 Jaguar Caravan Multiple and Cascading Boilers Nominal Internal Equivalent Length of Pipe, Feet Iron Pipe Diameter Size Inches Inches .622 .844 1.049 1-1/4 1.380 1,050 1-1/2 1.610 1,600 1,100 2.067 3,050 2,100 1,650 1,450 1,270 1,150 1,050 2-1/2 2.469 4,800 3,300 2,700 2,300...
  • Page 19: Jaguar Multiple Boiler System Control

    8 Jaguar boilers. Utilization of this feature requires one optional supply water sensor (Slant/Fin Part # 833-433) per Jaguar Multiple Boiler System. The boiler is programmed as the “master boiler” while the other Jaguar boilers are called the “follower boilers”.
  • Page 20 Proper polarity is critical for the power supply connections. Reversed piping instruction. A water supply system sensor (12 k ohm thermistor) polarity will cause boiler lockout. Proper grounding is critical for is required to operate and control the system. Slant/Fin system sensor boiler operation. part number is 833433000.
  • Page 21 Jaguar Caravan Multiple and Cascading Boilers...
  • Page 22 Jaguar Caravan Multiple and Cascading Boilers Figure 15.
  • Page 23 Changing System Setting” menus. 10.4 SETTING BOILERS CONTROL Fill system with water. See Installation and Operating Instructions of Jaguar J-390C boiler, Slant/Fin publica- tion J-40. Make sure flue pipes and air intake pipes are installed per venting application section of publication "RESET"...
  • Page 24 Jaguar Caravan Multiple and Cascading Boilers ND CH NGING SYSTEM SETTING - Table 4 VIEWING “To change system setting or perform system test” The menu is accessed by pressing and holding “SELECT” and “ENTER” buttons for 10 seconds. To access different modes: Press “ENTER” button. To change boiler setting: Press “UP or DOWN” button, then press “ENTER” WARNING: Only a trained, experienced service technician or installer should use this table.
  • Page 25 Jaguar Caravan Multiple and Cascading Boilers Maximum water target temp. 185 ° F Water Supply Target Temp. (° F) Minimum water target temp. Water reference temp. (default of 86°F) 68°F Outdoor Temp. (°F) Figure 19. Space Heating mode with outside sensor water set point graph.
  • Page 26 Jaguar Caravan Multiple and Cascading Boilers temperature flue temperature, outside temperature (if outside sensor 10.7 CHANGING SYSTEM WATER TEMPERATURE is used) and actual system water supply temperature on “Temperature Setting system supply water temperature for space heating Display” by selecting 1, 2, 3, 4, 5 or 6 on “Mode Display”. View number (see table 5): of boilers are on (includes boilers in lockout or error condition) on Press “SELECT”...
  • Page 27 Jaguar Caravan Multiple and Cascading Boilers Table 6 VIEWING FOLLOWER BOILER W TER TEMPER TURES Press “SELECT” button for viewing different modes on “MODE DISPLAY” MODE DISPLAY DESCRIPTION & TEMPERATURE DISPLAY NO FUNCTION blinking NO FUNCTION blinking NO FUNCTION blinking Temperature display shows actual supply water temperature.
  • Page 28 Jaguar Caravan Multiple and Cascading Boilers Table 8 FOLLOWER BOILER DISPL Y BO RD “Boiler Operation Status” MODE DISPLAY DESCRIPTION & TEMPERATURE DISPLAY Follower boiler is on stand-by mode. Temperature display shows boiler supply water Temp. Heating mode. Temperature display shows boiler supply water Temp. Frost protection mode.
  • Page 29 One special interface control is required for operation of each boiler in arrangements and electrical connections. the system. Use Slant/Fin interface kit (Part no. 830130). Kit includes 11.1.5 Outdoor and system water supply sensors: interface control and 3 different harnesses needed for connection of See Tekmar manual A275 and D070 for installation instruction Tekmar control to the interface and the boiler.
  • Page 30 Jaguar Caravan Multiple and Cascading Boilers NEUTRAL 120V/60HZ HARNESS P/N 83 2112 INTERFACE CONTROL SWITCH (MUST BE ON "OFF" POSITION) HARNESS HARNESS P/N 83 2115 P/N 83 2114 0-10V DC EXTERNAL SIGNAL 9 10 11 12 13 14 TEKMAR CONTROL 275 TERMINAL #7 & 8 (BOILER #1) OR BOILER TERMINALS #8 &...
  • Page 31 Jaguar Caravan Multiple and Cascading Boilers Table 9 VIEWING BOILER W TER TEMPER TURES Press “SELECT” button for viewing different modes on “MODE DISPLAY” MODE DISPLAY DESCRIPTION & TEMPERATURE DISPLAY NO FUNCTION blinking NO FUNCTION blinking NO FUNCTION blinking Temperature display shows actual boiler supply water temperature. Temperature display shows actual boiler return water temperature.
  • Page 32 Jaguar Caravan Multiple and Cascading Boilers DIAGNOSTIC ERROR CODES LOCKOUT ERRORS: Indicated by an “A” in the mode display. The reset button must be pressed to clear the error and retry operation. The temperature display shows the error code. ERROR CODE INDICATION REMEDY Check for steady sparking at electrodes.
  • Page 33 Jaguar Caravan Multiple and Cascading Boilers Indicated by an “E” in the mode display. Operation is automatically restored, once the BLOCKING ERRORS: condition returns to normal or is fixed. The temperature display shows the error code. Pressing the “Reset” button is not required. ERROR CODE INDICATION REMEDY...
  • Page 34 Jaguar Caravan Multiple and Cascading Boilers continued from page 24 ERROR CODE INDICATION REMEDY Check flue gas temperature, at the maximum firing rate and high water temperature. If the flue gas temperature reaches 212˚F, check the fuel input Excess Flue Temperature rate and combustion.
  • Page 35: Hybrid Boiler System

    With water tem- The water piping of a Slant/Fin hybrid boiler system is sim- peratures below 130F condensing boilers operate and ple. Slant/Fin recommends “injecting” the condensing boiler...
  • Page 36 Figure 22. Hybrid Boiler System. ©Slant/Fin Corp. 2011. Printed in the U.S.A. 611. Publication No. CJ-10-HWG SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600 FAX: (516) 484-5921 • Canada: Slant/Fin , Mississauga, Ontario LTD/LTEE www.slantfin.com...