Note: To properly check gas pressure, both inlet and
manifold pressures should be checked using the
valve pressure ports on the valve.
1)
Make sure the valve is in the off position.
2)
Loosen the screw at the outlet pressure test point, turn
captured screw counterclockwise 2 or 3 turns and then
placing tubing to gauge over test point.
3)
Attach tubing to a manometer using a 8mm I.D. hose.
4)
Light the pilot and turn the valve to "ON" position.
5)
The pressure check should be carried out with the unit
burning and the setting should be within the limits speci-
fi ed on the safety label.
normal
draft
COMBUSTION & VENTILATION AIR
WARNING: This appliance needs fresh air for safe opera-
tion and must be installed with provisions for adequate
combustion and ventilation air available to the room in
which it is to be operating.
This appliance installation must conform with local codes or in
the absence of local codes, with AS5601-2004 or NZS 5261.
Air for combustion is drawn in through the front of the unit, there-
fore, the front of the unit must be kept clear of any obstructions.
GAS PRESSURE TEST
The manifold pressure is controlled by a regulator built into the
gas control, and should be checked at the pressure test point.
Regency I43-1 ULTIMATE Gas Inbuilt Fireplace
downdraft
or blocked
fl ue
Spill Tube
Non-combustible
Scrap
INSTALLATION
is corrected. DO NOT BYPASS OR DISCONNECT
THIS SWITCH.