40 Installation

Grounding the 8010co chassis

Ground the 8010co chassis to avoid electrical hazard and ensure optimal
performance.
ATTENTION
Nortel recommends grounding the 8010co chassis before you connect power
cables or network cables to your switch.
Prerequisites
Procedure steps
Step
1
2
Copyright © 2008 Nortel Networks
.
Verify that you have the following tools and materials:
One single-hole cable lug that fits over one of the grounding studs.
A nut and locking washer for the grounding stud
A 6-AWG grounding wire long enough to connect to the ground
point
A 7/16-inch hex wrench to fasten the hardware in the correct order
Action
Locate the shelf grounding point on the rack.
The rack grounding point is a grounding strip located on the
back, base, top, or side.
ATTENTION
The rack grounding strip can look different than the one shown in
"Procedure job aid: Grounding the 8010co chassis" (page 41)
procedure job aid.
Attach the lug ends of the chassis ground cables to the rack
grounding strip using a 7/16-inch hex wrench to fasten the
hardware in the correct order.
For more information, see
8010co chassis" (page
Nortel Ethernet Routing Switch 8600
NN46205-310 02.01 Standard
30 May 2008
"Procedure job aid: Grounding the
41).
--End--