JSA3800 Appliance Rack Requirements

Related
Documentation

Additional Hardware Requirements

Copyright © 2015, Juniper Networks, Inc.
JSA3800 Appliance Description on page 3
JSA3800 Appliance Hardware Overview on page 4
Additional Hardware Requirements on page 17
The JSA3800 appliance can be installed in a four-post or two-post rack.
Table 8 on page 17
provides the details of requirements for rack size, clearance, airflow,
spacing of mounting brackets and flange holes, and connecting to the building structure.

Table 8: Rack Requirements for JSA3800

Rack Requirement
Specifications
Size
A 19 in. (48.3 cm) rack as defined in Cabinets, Racks, Panels, and Associated
Equipment (document number EIA-310-D) published by the Electronics
Industry Association (http://www.eia.org).
Clearance
The outer edges of the mounting brackets extend the width of either
chassis to 19 in. (48.3 cm).
The front of the chassis extends approximately 1.5 in. (3.81 cm) beyond
the mounting ears.
Spacing of
The holes within each rack set are spaced at 1-U [1.75 in. (4.5 cm)]. The
mounting bracket
device can be mounted in any rack that provides holes or hole patterns
and flange holes
spaced at 1-U [1.75 in. (4.5 cm)] increments. The holes within each rack
set are spaced at 1-U [1.75 in. (4.5 cm)].
The device can be mounted in any rack that provides holes or hole
patterns spaced at 1-U [1.75 in. (4.5 cm)] increments.
The mounting brackets and front-mount flanges used to attach the
chassis to a rack are designed to fasten to holes spaced at rack distances
of 1-U (3.5 in.).
The mounting holes in the mounting brackets provided with the device
are spaced 1.25 in. (3.2 cm) apart (top and bottom mounting hole).
Connecting to the
Always secure the rack in which you are installing the JSA3800 appliance
building structure
to the structure of the building. If your geographical area is subject to
earthquakes, bolt the rack to the floor. For maximum stability, also secure
the rack to ceiling brackets.
Additional Hardware Requirements on page 17
JSA3800 Appliance Physical Specifications on page 15
General Site Installation Guidelines for the JSA3800 Appliance on page 15
Before installing your JSA3800 appliances, ensure that you have access to the following
additional hardware components:
Chapter 4: Planning and Preparing the Site
17