INSTALLATION
Approved Venting Method 2: Through the Ceiling
Seal each pipe connection joint with high temperature RTV Silicone, to ensure the system is leak
free (Check with the specific pipe manufacturer's instructions before doing so).
If the pellet vent pipe being used is not a "Twist Lock" system, three (3) sheet metal screws are
required at each pipe joint.
Connect the pellet stove to outside combustion air using the kit included with your stove or using
an alternative method, as described in the "Outside Air" section, on page 15.
This venting method can also be modified so that the venting system runs horizontally through the
wall from the stove, then transitions to vertical and terminates above the roofline. When using this
modified version of this installation be certain to carefully follow the venting system
manufacturer's instructions diligently.
Please Note:
Installation diagrams are for reference purposes only and are not drawn to scale, nor meant to be used as plans for each
individual installation. Please follow all venting system requirements, maintain the required clearances to combustibles,
and follow all local codes
IMPORTANT! READ AND FOLLOW ALL INSTALLATION AND MAINTENANCE INSTRUCTIONS, INCLUDING CLEANING
THE UNIT AS SPECIFIED, AND REPLACING GASKETS ANNUALLY, AND PARTS AS NEEDED.
ENGLAND'S STOVE WORKS IS NOT RESPONSIBLE FOR ANY DAMAGE OR INJURY INCURRED DUE TO NEGLECT,
OR DUE TO UNSAFE INSTALLATION OR USAGE OF THIS PRODUCT. CALL TECHNICAL SUPPORT WITH ANY
Venting through the ceiling/roof may be the only feasible
venting option in some cases and is a factory recommended
installation.
When installing any venting system, Type L or Type PL pipe
must be used and all clearances to combustibles listed by the
pipe manufacturer must be strictly adhered to.
Use the pipe manufacturer's approved ceiling support for
passing through a combustible ceiling, as well as the required
fire stops, radiation shields, flashing and storm collar.
Be certain to follow the manufacturer's required height of
termination above the roof line, and maintain at least the
minimum clearances to combustibles.
Use an appliance collar where the pellet vent connects to
the exhaust output of the pellet stove and attach the appliance
collar to the exhaust blower output using three sheet metal
screws.
.
QUESTIONS.
For high altitude installations
(above 4,000 ft.), the vent pipe
should be increased from 3-inch
11
(3") to four-inch (4").