14. Detailed Settings in EEPROM of Outdoor Unit
Never use the DN code unlisted in the following table.
DN
Actuation of solenoid valve kit
AC
(EP closed)
C1 O
output change
2
CD Setting at heating thermostat OFF
Indoor fan mode setting when in
DD
discharge tube accumulated refrigerant
recovery control
Discharge tube accumulated refrigerant
DE
1
recovery control permission temperature
Discharge air temperature control with
E1
thermostat OFF additional time
Indoor unit fan selection when in cooling
ED
thermostat OFF
2
3
4
5
6
7
8
9
Item
0=Invalid (P), 1=Valid
0=Continuously set OFF (P)
1=Refrigerant leak prevention (normal OFF)
2=Refrigerant leak prevention (normal ON)
3=Pumpdown control
0=Invalid (P) , 1=Heating airflow prevention mode
0=Invalid , 1=stop (P) , 2=LL
-25=-13°F (-25°C), -20=-4°F (-20°C), -15=5°F (-15°C) ,,,,,
40=104°F (40°C) ,,,,, 55=131°F (55°C)
-20=-20 min , -19=-19 min ,,,,,
0=0 min (P) ,,,,, 10=10 min
0=Invalid (P) , 1=stop , 2=LL , 3=interval operation , 4=never
use
Setting No.
1 - 48
3WAY VRF SYSTEM
Control Functions
(P) : Factory preset mode