2. Detailed Settings Function
<Procedure of CZ-RTC3 / CZ-RTC5>
[
]
START
1
2
Keep pressing the
1
buttons simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the
3
LCD display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4
4.Test run
Sel.
Press the
2
menu.
If you wish to see the next screen instantly, press
5
the
or
Select "8. Detailed settings" on the LCD display
and press the
Maintenance func
6
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Sel.
The "Detailed settings" screen appears on the
7
LCD display.
Select the "Unit no." by pressing the
button for changes.
Detailed settings
8
Unit no.
3-1
Sel.
9
20:30 (THU)
CZ-RTC3 / CZ-RTC5
Fig. 5
,
and
20:30 (THU)
Page [
] Confirm
or
button to see each
button.
button.
20:30 (THU)
Page [
] Confirm
or
20:30 (THU)
Code no.
Set data
10
0001
Next
Select the "Code no." by pressing the
3
button.
Change the "Code no." by pressing the
button (or keeping it pressed).
Detailed settings
Unit no.
3-1
Sel.
Select the "Set data" by pressing the
4
button.
Select one of the "Set data" by pressing the
or
button.
Then press the
Detailed settings
Unit no.
3-1
Sel.
5
Select the "Unit no." by pressing the
button and press the
The "Exit detailed settings and restart?" (Detailed
setting-end) screen appears on the LCD display.
Select "YES" and press the
Detailed settings
Exit detailed settings
Unit no.
ALL
Sel.
4 - 10
3WAY VRF SYSTEM
Remote Controller Functions
or
20:30 (THU)
Code no.
Set data
10
0001
Next
or
button.
20:30 (THU)
Code no.
Set data
10
0001
[
] Confirm
or
button.
button.
20:30 (THU)
Code no.
Set data
and restart?
01
0002
YES
NO
Next